Diagnostics & troubleshooting 6 - 18 – Yaskawa F7 Drive User Manual User Manual

Page 143

background image

Diagnostics & Troubleshooting 6 - 18

Table 6.4 Auto-Tuning Fault Displays and Processing (continued)

Digital Operator

Display

Description

Probable Cause

Corrective Action

Er - 12

I-det. Circuit

Current Detection Fault

•Current exceeded the motor rated

current.

•Any of U/TI, V/T2, and W/T3 has

open-phase.

• Check that the motor is unloaded

(uncoupled and brake is released).

• Check Drive wiring and mounting.
• Check the motor connections for

continuity (on Drive output terminals
and in motor junction box).

Er - 13

Leakage

Inductance Fault

Leakage Inductance Fault

Auto-Tuning did not finish within
the set time.
Auto-Tuning result is outside the
parameter setting range.

• Check Auto-Tuning input data (T1

parameters).

• Check motor wiring for proper

connection configuration.

End - 1

V/F Over Setting

V/F Settings Alarm
Displayed after Auto-Tuning is
complete.

The torque reference exceeded
100%, and the no-load current
exceeded 70% during Auto-Tuning.

• Check and correct the motor

settings (T1 parameters).

• If the motor is coupled to the load,

disconnect the motor from the
load.

End - 2

Saturation

Motor Core Saturation Fault
Detected only for rotational
Auto-Tuning.

During Auto-Tuning, the measured
values of motor iron-core saturation
coefficient 1 and 2 (E2-07 and
E2-08) exceeded its setting range. A
temporary value was set:
E2-07 = 0.75, E2-08 = 0.50.

• Check Auto-Tuning input data (T1

parameters).

• Check the motor wiring.
• If the motor and the load are

connected, disconnect the motor
from the load.

End - 3

Rated FLA Alm

Rated Current Setting Alarm
Displayed after Auto-Tuning is
complete.

During Auto-Tuning, the measured
value of motor rated current (E2-01)
was greater than the set value.

• Check the motor rated current

value (E2-01).

End - 4

Slip Lower Limit

<3021>

Slip Lower Limit
Adjusted slip value fell below the
lower limit.

During stationary Auto-Tuning, the
slip value has fallen to 0.2 Hz or
below.

• Check the input data.
• Perform a Rotational Auto-Tuning.

if possible. If not possible, perform
a stationary Auto-Tuning 2.