Motor Setup

E2-01 Motor Rated Current

Setting Range:

Model Dependent

Factory Default: Model Dependent

The Motor Rated Current parameter (E2-01) is used by the Drive to protect the motor and for proper Vector control when
using Open Loop Vector or Flux Vector control methods (A1-02 = 2 or 3). The motor protection parameter L1-01 is enabled
by default. Set E2-01 to the full load amps (FLA) stamped on the motor’s nameplate.
During Auto-Tuning, it is required for the operator to enter the motor’s rated current (T1-04) in the Auto-Tuning menu. If the
Auto-Tuning operation completes successfully, the value entered into T1-04 will automatically be written into E2-01.

E2-04 Number of Motor Poles

Setting Range:

2 to 48

Factory Default: 4

This parameter sets the number of motor poles. During Auto-Tuning, it is required for the operator to enter the number of
motor poles (T1-06) in the Auto-Tuning menu. If the Auto-Tuning operation completes successfully, the value entered into
T1-06 will automatically be written into E2-04.

E2-11 Motor Rated Power

Setting Range:

0.00 to 650.00kW

Factory Default: Varies by kVA

This parameter sets the motor rated power is set in kilowatts (kW).
1HP = 0.746kW

During Auto-Tuning, it is required for the operator to enter the motor’s rated power (T1-02) in the Auto-Tuning menu. If the
Auto-Tuning operation completes successfully, the value entered into T1-02 will automatically be written into E2-11.

PG Option

F1-01 PG Pulses / Revolution

Setting Range:

0 to 60000

Factory Default: 1024

If a PG encoder option is used with the Drive, the number of PG pulses per motor revolution (PPR) must be set. During
Auto-Tuning, it is required for the operator to enter the PG pulses per revolution (T1-08) in the Auto-Tuning menu. If the
Auto-Tuning operation completes successfully, the value entered into T1-08 will automatically be written into F1-01.