Electrical installation 2 - 5 – Yaskawa F7 Drive User Manual User Manual
Page 32

Electrical Installation 2 - 5
Table 2.2 480Vac Wire Sizes and Connector Specifications
Drive Model
CIMR-F7U
Terminal Symbol
Terminal
Screws
Clamping
Torque
lb. in.
(N•m)
Possible Wire
Sizes AWG
(mm
2
)
*
1
Recommended
Wire Size AWG
(mm
2
)
*2
Wire Type
40P4
R/L1, S/L2, T/L3,
,
1,
2, B1, B2
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
14 to 10
(2 to 5.5)
14
(2)
600Vac
UL Approved
vinyl-sheathed
or equivalent
40P7
R/L1, S/L2, T/L3,
,
1,
2, B1, B2
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
14 to 10
(2 to 5.5)
14
(2)
41P5
R/L1, S/L2, T/L3,
,
1,
2, B1, B2
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
14 to 10
(2 to 5.5)
14
(2)
42P2
R/L1, S/L2, T/L3,
,
1,
2, B1, B2
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
14 to 10
(2 to 5.5)
14
(2)
43P7
44P0
R/L1, S/L2, T/L3,
,
1,
2, B1, B2
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
14 to 10
(2 to 5.5)
12
(3.5)
14
(2)
45P5
R/L1, S/L2, T/L3,
,
1,
2, B1, B2
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
12 to 10
(3.5 to 5.5)
12
(3.5)
14 to 10
(2 to 5.5)
14
(2)
47P5
R/L1, S/L2, T/L3,
,
1,
2, B1, B2
U/T1, V/T2, W/T3
M4
15.6
(1.8)
10
(5.5)
10
(5.5)
12 to 10
(3.5 to 5.5)
12
(3.5)
4011
R/L1, S/L2, T/L3,
,
1,
2, B1, B2
M5
21.99
(2.5)
10 to 6
(5.5 to 14)
8
(8)
U/T1, V/T2, W/T3
10
(5.5)
4015
R/L1, S/L2, T/L3,
,
1,
2,B1, B2
U/T1, V/T2, W/T3
M5
21.99
(2.5)
8 to 6
(8 to 14)
8
(8)
M5
21.99
(2.5)
10 to 6
(5.5 to 14)
10
(5.5)
M6
35.2 to 43.99
(4.0 to 5.0)
4018
R/L1, S/L2, T/L3,
,
1,
2
M6
35.2 to 43.99
(4.0 to 5.0)
8 to 2
(8 to 38)
6
(14)
U/T1, V/T2, W/T3
8
(8)
B1, B2
M5
21.99
(2.5)
8
(8)
8
(8)
M6
35.2 to 43.99
(4.0 to 5.0)
8 to 4
(8 to 22)
8
(8)
4022
R/L1, S/L2, T/L3,
,
1,
3, R1/L11, S1/L21,
T1/L31
M6
35.2 to 43.99
(4.0 to 5.0)
N/A
4
(22)
U/T1, V/T2, W/T3
6
(14)
M8
79.2 to 87.97
(9.0 to 10.0)
N/A
6
(14)