Basic Programming 5 - 6

When the output frequency has dropped below the DC Injection Start Frequency (b2-01) or the minimum output frequency
(E1-09) (whichever is greater), deceleration will stop and DC current will be injected into the motor at the current level set in
b2-02 for the time set in b2-04.

Fig 5.3 Deceleration to Stop

The actual deceleration time can be determined by the following formula:

1: Coast to stop:

When the run command is removed, the Drive will turn off its output transistors. The friction of the driven
equipment will eventually overcome any residual inertia of the system and the motor will stop.

Fig 5.4 Coast to Stop

IMPORTANT

If S-Curve characteristics are set in the Drive programming, they will add to the total time to stop.

IMPORTANT

After a stop is initiated, subsequent run commands will be ignored until the Minimum Baseblock Time
(L2-03) has expired.

ON

OFF

Run Command

Output Frequency

Deceleration Time (C1-02)

DC Injection Braking

100 %

0 %

DC Injection Brake Time

when Stopping (b2-04)

DC Injection Start

Frequency (b2-01)

on time

decelerati

Active

x

04)

(E1

frequency

Maximum

command

stop

of

at time

frequency

Output

stop

to

Time

=

ON

OFF

Run Command

Output Frequency

100 %

0 %