Specifications C - 5

The following specifications apply to both 200Vac and 400Vac Class Drives.

Table C.3 Common F7 Drive Specifications

Model Number

CIMR-F7U

Specification

Control method

Sine wave PWM

V/F control, V/F control with PG, Open Loop Vector control, Flux Vector Control

Speed control range

100:1 (1000:1 with PG)

Speed control accuracy

±0.2% (±0.02% with PG) (77

°F ± 50°F) (25°C ± 10°C)

Speed response

5Hz (30Hz with PG)

Torque limit

Can be set by parameter, analog input, or serial communication: 4 quadrant control

Torque accuracy

±5%

Torque response

20Hz (40Hz with PG)

Frequency control range

0.01 to 400.00Hz

Frequency accuracy
(temperature characteristics)

Digital references: ± 0.01% (14

°F to 104°F) (-10°C to +40°C)

Analog references: ±0.1% (77

°F ± 50°F) (25°C ±10°C)

Frequency setting resolution

Digital references: 0.01Hz

Analog references: 0.03 @60Hz (10 bit with sign)

Output frequency resolution

0.001Hz

Analog setting signal

-10 to +10Vdc, 0 to +10Vdc, 4 to 20mA

Acceleration/Deceleration
time

0.0 to 6000.0 sec (4 selectable combinations of independent acceleration and deceleration settings)

Internal braking torque

Approximately 20%

Main control functions

Restarting from momentary power loss, bi-directional speed search, Overtorque/Undertorque detection, 17 preset
speeds, acceleration/deceleration time changes, S-curve acceleration, 3-wire sequence, Auto-Tuning, cooling fan ON/
OFF control, torque compensation, speed control/torque control switch, jump frequencies, upper and lower limits for
frequency references, DC braking for starting and stopping, high-slip braking, PID control (with sleep function),
energy-saving control, Modbus communications (RS-485/422, 19.2 kbps maximum), fault reset, and copy function.

Motor protection

UL recognized electronic thermal overload relay (I

2

T)

Instantaneous overcurrent
protection

Stops at approximately 200% of rated output current

Main circuit protection

Fuse in DC bus circuit

Overload protection

Normal Duty (C6-01 = 2) - Approximately 110% of rated output current for 60 seconds

Heavy Duty (C6-01 = 0) - 150% of rated output current for 60 seconds

Model 2110 - 138% of rated output for 60 seconds

Models 4220/4300 - 150% of rated output for 45 seconds

Overvoltage protection

208-240Vac: Stops when main-circuit DC voltage is above 410Vdc

480Vac: Stops when main-circuit DC voltage is above 820Vdc

Undervoltage protection

208-240Vac: Stops when main-circuit DC voltage is below 190Vdc

480Vac: Stops when main-circuit DC voltage is below 380Vdc

Momentary power loss
ride-thru

Two selectable methods: 1. Time base for up to 2 seconds. 2. Until control power is active.

Heatsink over-temperature

Protection by thermistor

Stall prevention

Stall prevention during acceleration, deceleration, and running

Ground fault protection

Protection by electronic circuit (50% of inverter rated current)

DC bus charge

Lit when the main circuit DC voltage is approximately 50Vdc or more

Enclosure Type

Enclosed wall-mounted type (NEMA 1): CIMR-F7U20P4 thru 2018 and 40P4 thru 4018

Open chassis type (IP00):

CIMR-F7U2022 thru 2110 and 4030 thru 4300

Ambient operating
temperature

14

°F to 104°F (-10°C to 40°C) NEMA 1 type

14

°F to 113°F (–10°C to 45°C) Open chassis type

Ambient operating humidity

95% max. (with no condensation)

Storage temperature

-4

°F to 140°F (- 20°C to + 60°C) short-term temperature during transportation

Mounting location

Indoor (no corrosive gas, dust, etc.)

Altitude

3300 feet (1000 m) (higher altitudes by derate)

Vibration

10 to 20Hz, 32 ft/sec

2

(9.8 m/s

2

) max.; 20 to 50Hz, 6.5 ft/sec

2

(2 m/s

2

) max.