beautypg.com

Accel/decel time, Accel/decel time -8, Basic programming 5 - 8 – Yaskawa F7 Drive User Manual User Manual

Page 109

background image

Basic Programming 5 - 8

Accel/Decel Time

C1-01 Acceleration Time 1

C1-02 Deceleration Time 1

Setting Range:

0.0 to 6000.0

Factory Default: 10.0sec

C1-01 (Acceleration Time 1) sets the time to accelerate from zero to maximum output frequency (E1-04). C1-02 (Deceleration
Time 1) sets the time to decelerate from maximum output frequency to zero. C1-01 and C1-02 are the factory default active
accel/decel settings. Alternate accel/decel settings (C1-03 through C1-08) can be activated by multi-function digital inputs
(H1-0 = 7 and 1A), or specified by the switch over frequency (C1-11). See Fig 5.7 below.

Fig 5.7 Acceleration/deceleration Time Switch Over Frequency

C1-07 Rate

C1-01 Rate

C1-02 Rate

C1-08 Rate

C1-11

Out

p

ut

Fr

eque

nc

y

Time