Standard drive specifications, 240vac, Specifications c - 2 – Yaskawa F7 Drive User Manual User Manual
Page 215

Specifications C - 2
Standard Drive Specifications
The standard Drive specifications are listed in the following tables.
208-240Vac
Table C.1 208-240Vac Drive Specifications
208-240Vac Drives
208-230Vac Drives
Model Number CIMR-
F7U
20P4
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015 2018 2022
2030
2037
2045
2055
2075
2090
2110
*5
Rated output
capacity
(kVA)
1.2
1.6
2.7
3.7
5.7
8.8
12.0
17.0
22.0
27.0
32.0
44.0
55.0
69.0
82.0
110.0
130.0 140.0
Horsepower
*2
0.5/0.75
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
Rated output
current
(A)
3.2
4.2
7.0
9.6
15.2
23.0
31.0
45.0
58.0
71
85.0
115.0
145.0 180.0
215
283.0
346.0 360.0
Overload capacity
*3
(% of rated output
current for 60 sec)
150
138
*3
Current limit (% of
rated output current)
150
138
*3
Carrier frequency
*5,*7
2kHz
Maximum output
frequency
300.0Hz
Rated output
capacity
(kVA)
1.4
1.8
3.0
4.1
6.4
8.8
12.0
18.0
23.0
29.0
34.0
44.0
62.0
73.0
82.0
120.0
140.0 160.0
Horsepower
*2
0.5/0.75
1
2
3
5
7.5
10
15
20
25
30
40
50/60
75
-
100/125
150
-
Rated output
current
(A)
3.6
4.6
7.8
10.8
16.8
23.0
31.0
46.2
59.4
74.8
88.0
115.0
162.0 192.0
215
312.0
360.0 415.0
Overload capacity
*3
(% of rated output
current for 60 sec.)
107
107
108
107
107
120
120
117
117
114
116
120
107
113
120
109
115
120
Current limit (% of
rated output current)
120
Carrier frequency
(kHz)
*6
10
10
10
8
10
15
15
8
10
10
10
10
5
5
8
2
2
2
Maximum output
frequency
400.0Hz
Maximum output
voltage
3-phase; 200, 208, 220, 230, or 240Vac
(Proportional to input voltage)
Rated voltage
Rated frequency
3-phase, 200/208/220/230/240Vac, 50/60Hz
3-phase, 200/208/220/230Vac, 50/60Hz
Rated input current -
Heavy Duty
*1
(A)
3.8
4.9
8.4
11.5
18
24
37
52
68
84
94
120
160
198
237
317
381
396
Rated input current -
Normal Duty
*1
(A)
4.3
5.5
9.4
13
20
24
37
53
70
89
98
120
180
212
237
350
396
457
Allowable voltage
fluctuation
+ 10%, - 15%
Allowable frequency
fluctuation
±5%
Measures
for power
supply
harmonics
DC
Reactor
Optional
Built-in
12-Pulse
Rectification
Not possible
Possible
*4
*1 The difference between Heavy Duty ratings and the Normal Duty ratings for the Drive are the rated input and output current, overload capacity, carrier frequency, current limit, and maxi-
mum output frequency. Parameter C6-01 must be set to value of “0” for Heavy Duty ratings and “2” for Normal Duty ratings. Factory default is Heavy Duty (C6-01=0).
*2 Horsepower ratings are based on 230V or 460V NEC Table 430.150. The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and Drive,
be sure that the Drive's rated output current is appropriate for the motor's rated current.
*3 Model 2110 has an overload rating of 138% of rated output current for 60 seconds and a current limit rating of 138%. Models 4220 and 4300 have an overload rating of 150% of rated output
current for 45 seconds and a current limit rating of 150%.
*4 When setting the carrier frequency above the factory default, the Drive must be derated.
*5 Heavy Duty ratings for models 2110, 4220 and 4300 are effective in software version VSF103021 and higher.
*6 Each value shown is the Maximum carrier frequency and default carrier frequency.
*7 The carrier frequency for Heavy Duty is default to 2 kHz. Software version VSF103021 and higher may allow the carrier frequency to be increased above 2 kHz with a reduction in
continuous rated output current. Refer to C6-02 in Chapter 5 for further details.
O
u
tpu
t rat
ing
s
Hea
v
y Duty
*
1
Norma
l Duty
*
1
Pow
er s
u
pp
ly c
h
ar
act
er
ist
ics
C
ont
ro
l c
h
arac
te
ri
st
ics