Basic programming 5 - 19 – Yaskawa F7 Drive User Manual User Manual

Page 120

background image

Basic Programming 5 - 19

Table 5.6 lists the factory settings of V/F patterns when open loop vector or flux vector control method is selected
(A1-02 = 2 or 3).

Table 5.6 V/F Pattern for 200V Class Drives

Parameter No.

Name

Unit

Factory Setting

Open Loop Vector

Flux Vector

E1-04

Max. Output
Frequency

Hz

60.0

60.0

E1-05

Max. Output Voltage

V

230.0

230.0

E1-06

Base Frequency

Hz

60.0

60.0

E1-07

Mid. Output
Frequency

V

3.0

0.0

E1-08

Mid. Output Voltage

V

12.6

0.0

E1-09

Min. Output
Frequency

Hz

0.5

0.0

E1-10

Min. Output Voltage

V

2.3

0.0

1. For 400V class units, the voltage values are twice that of 200V class units.
2. These default values are for open loop vector or flux vector control methods (A1-02 = 2 or 3)