background image

Basic Programming 5 - 11

Preset Reference

d1-01 Frequency Reference 1

d1-02 Frequency Reference 2

d1-03 Frequency Reference 3

d1-04 Frequency Reference 4

Setting Range:

0.0 to E1-04 (Maximum Output Frequency)

Factory Default: 0.0Hz

d1-17 Jog Reference

Setting Range:

0.0 to E1-04 (Maximum Output Frequency)

Factory Default: 6.0Hz

Up to 17 preset references (including Jog Reference) can be set through multi-function inputs S3 to S8. The first 4 preset
references and Jog Reference are accessible through the Quick Setting menu. It is a two-step process to set the Drive up for
preset speeds. First, d1-01 through d1-04 and d1-17 must be programmed with the desired preset speeds and the desired jog
speed, respectively. Next, three of the Drive’s digital inputs need to be programmed and wired as Multi-step Speed Reference
1, Multi-step Speed Reference 2, and Jog Frequency.

As shown in the above table, it is possible to use analog inputs in place of Frequency Reference 1 and Frequency Reference 2.

If b1-01 = 1, then the analog input A1 will be used instead of Frequency Reference 1 for the first preset speed. If b1-01=0
then Frequency Reference 1 (d1-01) will be used.

If H3-05 = 2, then the analog input A2 will be used instead of Frequency Reference 2 (d1-02) for the second preset speed.

If H3-05

≠ 2, then Frequency Reference 2 will be used.

Table 5.2 Preset Speed

Preset Speed

Terminal

programmed

as Multi-step

Reference 1

Terminal

programmed
as Multi-step

Reference 2

Terminal

programmed

as Jog

Reference

Details

1

OFF

OFF

OFF

Frequency Reference 1 (d1-01) or analog input A1

2

ON

OFF

OFF

Frequency Reference 2 (d1-02) or analog input A3

3

OFF

ON

OFF

Frequency Reference 3 (d1-03)

4

ON

ON

OFF

Frequency Reference 4 (d1-04)

5

-

-

ON*

Jog Frequency (d1-17)

* The Jog Frequency input is given priority over the multi-step speeds.

IMPORTANT

The programming of d1-01 through d1-17 will be in the units specified by the display scaling parameter (o1-03).