Chiller requirements

Caution:

the cooling system must have a filter that allows the coolant to meet the

specifications for particles shown below. Failure to use a filter capable

of meeting the particle requirements can cause damage to expensive

optical components and could be cause for denial of warranty claims on

these components.

Coolant

Acceptable types of coolant

Distilled water

Drinkable tap water

Water/glycol mixture (see “Usage of inhibitors/additives” below)
Deionized water is NOT allowed

Particles

< 100 μm in diameter.

Conductivity

50 – 500 microSiemens/cm

pH

5.5 – 9.0

Usage of
inhibitors/additives

Usage of inhibitors or additives is allowed if the mixture meets specifications regarding

particles, conductivity, and pH.
As an example, Hypertherm torch coolant (028872) in 70/30 proportion is allowed

Maximum pressure

5.4 bar (80 psi)

Fitting connections

3/4 in female NPT

Coolant temperature range

25° C (+/– 5° C)

Flow rates

HFL010 (1.0 kW) laser

20 liters (5 gal) per minute minimum

HFL015 (1.5 kW) laser

40 liters (10 gal) per minute minimum

HFL020 (2.0 kW) laser

40 liters (10 gal) per minute minimum

HFL030 (3.0 kW) laser

40 liters (10 gal) per minute minimum

Cooling capacity

HFL010 (1.0 kW) laser

5 kW (17,100 BTU/hr)

HFL015 (1.5 kW) laser

8 kW (27,300 BTU/hr)

HFL020 (2.0 kW) laser

10 kW (34,125 BTU/hr)

HFL030 (3.0 kW) laser

12 kW (40,946 BTU/hr)