Chiller requirements
Caution:
the cooling system must have a filter that allows the coolant to meet the
specifications for particles shown below. Failure to use a filter capable
of meeting the particle requirements can cause damage to expensive
optical components and could be cause for denial of warranty claims on
these components.
Coolant
Acceptable types of coolant
Distilled water
Drinkable tap water
Water/glycol mixture (see “Usage of inhibitors/additives” below)
Deionized water is NOT allowed
Particles
< 100 μm in diameter.
Conductivity
50 – 500 microSiemens/cm
pH
5.5 – 9.0
Usage of
inhibitors/additives
Usage of inhibitors or additives is allowed if the mixture meets specifications regarding
particles, conductivity, and pH.
As an example, Hypertherm torch coolant (028872) in 70/30 proportion is allowed
Maximum pressure
5.4 bar (80 psi)
Fitting connections
3/4 in female NPT
Coolant temperature range
25° C (+/– 5° C)
Flow rates
HFL010 (1.0 kW) laser
20 liters (5 gal) per minute minimum
HFL015 (1.5 kW) laser
40 liters (10 gal) per minute minimum
HFL020 (2.0 kW) laser
40 liters (10 gal) per minute minimum
HFL030 (3.0 kW) laser
40 liters (10 gal) per minute minimum
Cooling capacity
HFL010 (1.0 kW) laser
5 kW (17,100 BTU/hr)
HFL015 (1.5 kW) laser
8 kW (27,300 BTU/hr)
HFL020 (2.0 kW) laser
10 kW (34,125 BTU/hr)
HFL030 (3.0 kW) laser
12 kW (40,946 BTU/hr)