• When the internal event configuration 1 operation type is set at [0: No event], the
internal event main setting, sub setting, and hysteresis are not displayed.
• For details about internal event operation with main setting, sub setting, and
hysteresis,
List of internal event operations (on pages 5-39 to 5-41)
■
ON delay and OFF delay
ON delay is a function that delays the timing, at which the internal event status is
changed from OFF to ON.
OFF delay is a function that delays the timing, at which the internal event status is
changed from ON to OFF.
However, when the operation type is set at [20: Loop diagnosis 1], [21: Loop
diagnosis 2], [22: Loop diagnosis 3], or [32: Timer], the ON delay and OFF delay
are operated as another function.
For details,
List of internal event operations (on pages 5-39 to 5-41)
ON delay and OFF delay can be set.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Setting display/bank)
Display
Contents
Initial value
User level
Internal Event 1 ON delay
(Parameter setting/Event
bank)
0.0 to 999.9s (Delay time unit is “0.1s”.)
0 to 9999s (Delay time unit is other than
“0.1s”.)
0.0s or 0s
High function
Internal Event 1 OFF delay
(Parameter setting/Event
bank)
0.0 to 999.9s (Delay time unit is “0.1s”.)
0 to 9999s (Delay time unit is other than
“0.1s”.)
0.0s or 0s
Internal Event 2 ON delay
(Parameter setting/Event
bank)
0.0 to 999.9s (Delay time unit is “0.1s”.)
0 to 9999s (Delay time unit is other than
“0.1s”.)
0.0s or 0s
Internal Event 2 OFF delay
(Parameter setting/Event
bank)
0.0 to 999.9s (Delay time unit is “0.1s”.)
0 to 9999s (Delay time unit is other than
“0.1s”.)
0.0s or 0s
Internal Event 3 ON delay
(Parameter setting/Event
bank)
0.0 to 999.9s (Delay time unit is “0.1s”.)
0 to 9999s (Delay time unit is other than
“0.1s”.)
0.0s or 0s
Internal Event 3 OFF delay
(Parameter setting/Event
bank)
0.0 to 999.9s (Delay time unit is “0.1s”.)
0 to 9999s (Delay time unit is other than
“0.1s”.)
0.0s or 0s
Internal Event 4 ON delay
(Parameter setting/Event
bank)
0.0 to 999.9s (Delay time unit is “0.1s”.)
0 to 9999s (Delay time unit is other than
“0.1s”.)
0.0s or 0s
Internal Event 4 OFF delay
(Parameter setting/Event
bank)
0.0 to 999.9s (Delay time unit is “0.1s”.)
0 to 9999s (Delay time unit is other than
“0.1s”.)
0.0s or 0s