4 at (auto tuning) function, Starting procedures, Stopping procedures – Nor-Cal SDC15 Controller User Manual
Page 71: 5 - 4 at (auto tuning) function
5 - 4
AT (auto tuning) Function
5-21
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
The AT (auto tuning) function is used in the following cases:
• The PID constants are set automatically with the control method set at “Fixed PID” ([CtrL = 1]).
• The PV rise is slow or overshoot is large in the control with the PID constants, which have been set automatically
using the ST function.
• The PV rise becomes slow or overshoot becomes large with the control method set at ST ([CtrL] = 2).
The AT function can be used when the control method is set at either “Fixed PID” ([CtrL] = 1) or ST ([CtrL = 2]).
■
Starting procedures
(1) Make sure that the PV input or operation end (heater power, etc.) is
controllable.
(2) Make sure that the mode indicator [rdy] is off and the operation is in the RUN
mode. If the indicator [rdy] is lit and the operation is in the READY mode,
change the mode to the RUN mode.
(3) Make sure that the mode indicator [man] is off and the operation is in the
AUTO mode. If the indicator [man] is lit and the operation is in the MANUAL
mode, change the mode to the AUTO mode.
(4) Set the parameter setting [AT Stop/Start] to “AT start ([At] = [At.on])”.
■
Stopping procedures
The AT function is completed automatically. To stop the AT function, which is
running, change the parameter setting [AT Stop/Start] to AT stop ([At] = [At.oF]).
Additionally, the AT function is stopped when changing the READY mode to the
MANUAL mode.
●
Display during execution of AT
The decimal point at the 1st digit of the display No. 1 (right end digit) flashes
twice repeatedly while the AT function is running. When the AT function is
completed and the PID constants are changed, this LED goes off.
●
Operation during execution of AT
The AT function calculates the PID constants using the limit cycle.
(1) When the AT function is started, a point, where the SP and PV deviations are
split to “2:1”, is determined as ON/OFF change point of the MV (manipulated
variable).
(2) When the limit cycle is judged as stable, the PID constants are changed and the
AT function is completed.