Nor-Cal SDC15 Controller User Manual
Page 212
13-4
Chapter 13. SPECIFICATIONS
●
Isolation between input and output
Portions enclosed by solid lines are insulated from other signals.
Whether or not inputs and outputs are provided may vary depending on the model.
✽
In case of the independent contacts, the output 1 and the output 2 are isolated.
●
Environment conditions
• Standard conditions
Ambient temperature: 23±2˚C
Ambient humidity:
60±5%RH
Power supply voltage: AC power model, 105Vac±1%, 50/60Hz±1Hz
DC power model, 24Vac±1%, 50/60Hz±1Hz
24Vdc±5%
Vibration:
0m/s
2
Shock:
0m/s
2
Mounting angle:
(Reference plane) ±3˚
• Operating conditions
Ambient temperature: 0 to 50˚C (0 to 40˚C for tight-mounting)
Ambient humidity:
10 to 90%RH (No condensation allowed.)
Power supply voltage: AC power model, 85 to 264Vac, 50/60Hz±2Hz
(Rating: 100 to 240Vac, 50/60Hz)
DC power model, 21.6 to 26AVac, 50/60Hz±2Hz/21.6 to 52.8Vdc
(Rating: 24Vac, 50/60Hz 24 to 48Vdc)
Vibration:
0 to 2m/s
2
(10 to 60Hz for 2 hrs. in each of the X-, Y-, and Z-direction)
Shock:
0 to 10m/s
2
Mounting angle:
(Reference plane) ±10˚
• Transportation conditions
Ambient temperature: -20 to +70˚C
Ambient humidity:
10 to 95%RH (No condensation allowed.)
Power supply
Control output 1
PV input
Control output 2
CT input 1
Internal circuit
CT input 2
Event output 1
✽
Loader communication
Event output 2
✽
Digital input 1
Event output 3
Digital input 2
RS-485 communication