Decimal point position – Nor-Cal SDC15 Controller User Manual
Page 54
■
Decimal point position
When the PV input type is L (DC voltage/DC current) or when the PV input type
is a part of the PV input range type of R (RTD), the decimal point position of the
PV input can be set.
Handling Precautions
As this setting is changed, the decimal point position of the parameters
related to the decimal point position of the PV input is also changed.
Actually, the decimal point position of the following settings are
changed:
SP setting
SP low limit/high limit setting
SP up ramp/down ramp setting
Event setting and continuous output setting related to PV
Event setting and continuous output setting related to SP
Event setting and continuous output setting related to deviation
(absolute deviation)
Note
• For the display conditions, setting range and initial value of range numbers
(C01), refer to:
5-1 (PV Input), PV range tables.(on page 5-2).
5-4
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Output after PV square root extraction (PVout)
100%FS
PVin
Dropout value (variable change from 0.1 to 100.0%)
0
100%FS
0
Y = Xin/100 X100
Item (Setting display/bank)
Display
Contents
Initial value
User level
Decimal point position
(Setup setting/Setup bank)
0: No decimal point
1: 1 digit below decimal point
2: 2 digits below decimal point
3: 3 digits below decimal point
0
Simple,
Standard,
High function