Event channel def, Input bit function – Nor-Cal SDC15 Controller User Manual
Page 84

■
Event channel def.
When the operation type is the timer start/stop, a target Event channel can be set.
• When the operation type of the same internal contact No. is set at “Timer
stop/start”, the display and setting can be made.
■
Input bit function
Four kinds of input bit functions are provided. What function of four functions is
used or is not used can be set.
• When the set value is “0”, the input bit function is not used and the default input
is used. The following shows the default input of each internal contact:
Internal Contact 1: DI (digital input) 1
Internal Contact 2: DI (digital input) 2
Internal Contact 3: OFF status
• In the input bit function, the logical operations (AND, OR) of each of internal
contacts 1 to 3 are combined. In input bit functions 1 to 4, the combination of the
logical operations may vary. The following shows one logical operation:
Logical AND
Logical OR
OFF and OFF = OFF
OFF or OFF = OFF
ON and OFF = OFF
ON or OFF = ON
ON and ON = ON
ON or ON = ON
• “OFF” is “contact open (OPEN)” or “0” when expressed using the numerical
value.
• “ON” is “contact close (CLOSE)” or “1” when expressed using the numerical
value.
5-34
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Setting display/bank)
Display
Contents
Initial value
User level
Internal Contact 1 Event
channel def.
(Setup setting/DI
Assignment bank)
0: Every Internal Event
1 to 5: Internal Event number
0
High function
0
Internal Contact 2 Event
channel def.
(Setup setting/DI
Assignment bank)
0
Internal Contact 3 Event
channel def.
(Setup setting/DI
Assignment bank)
Item (Setting display/bank)
Display
Contents
Initial value
User level
Internal Contact 1 Input bit
function
(Setup setting/DI
Assignment bank)
0: Not used (Default input)
1: Function 1 ((A and B) or (C and D))
2: Function 2 ((A or B) and (C or D))
3: Function 3 (A or B or C or D)
4: Function 4 (A and B and C and D)
0
High function
0
Internal Contact 2 Input bit
function
(Setup setting/DI
Assignment bank)
0
Internal Contact 3 Input bit
function
(Setup setting/DI
Assignment bank)