Di assignment of lsp group selection, Sp ramp unit – Nor-Cal SDC15 Controller User Manual
Page 79
5-29
■
DI Assignment of LSP group selection
The LSP group selection can be set for internal contacts 1 to 3 using the DI
Assignment.
• Details of LSP group selection with the internal contact function
The following shows the LSP group selection value according to the ON/OFF
status of each internal contact:
LSP group selection (0/+1)
OFF: 0
ON: 1
LSP group selection (0/+2)
OFF: 0
ON: 2
LSP group selection (0/+4)
OFF: 0
ON: 4
The value, that "1" is added to the sum of the LSP group selection values
according to the ON/OFF status of each internal contact, becomes the LSP group
number.
For example, when the sum of LSP group selection values of internal contact 1 to
3 is "1", the LSP group number becomes "2".
• Even though the LSP system group is "1", the display and setting can be made,
but the LSP group selection with the internal contact function becomes invalid.
■
SP ramp unit
The unit of the SP up/down ramp can be set.
• "0.1U" shows that the decimal point position of the PV is shifted one digit
rightward.
Example: When the thermocouple input is in a range of -200 to +1200˚C, "0.1U"
is "0.1˚C ".
Example: When the DC voltage input is in a range of 0.0 to 100.0, "0.1U" is
"0.01".
Handling Precautions
When using the DC voltage/DC current input with setting of 3 digits
after the decimal point, "0.1U" is "0.0001".
However, the SP up ramp/SP down ramp setting cannot display 4
digits after the decimal point, the value is displayed without use of the
decimal point.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Setting display/bank)
Display
Contents
Initial value
User level
DI Assignment Internal
Contacts 1 to 3
Operation type
(Setup setting/DI
Assignment bank)
0: No function
1: LSP group selection (0/+1)
2: LSP group selection (0/+2)
3: LSP group selection (0/+4)
4 to 20: Other functions
0
Simple,
Standard,
High function
0
0
Item (Setting display/bank)
Display
Contents
Initial value
User level
SP ramp unit
(Setup setting/Setup bank)
0: 0.1U/s
1: 0.1U/min
2: 0.1U/h
0
High function