Handling precautions, Pv input range table (dc voltage/dc current) – Nor-Cal SDC15 Controller User Manual
Page 52

●
PV input range table (Thermocouple)
●
PV input range table (RTD)
*1: The accuracy of a B thermocouple is ±5%FS for a
range of 260˚C or less, ±1%FS for 260 to 800˚C.
The indicated low limit for a B thermocouple is 20˚C.
However, if ROM version 1 of the instrument
information bank (
Id02
) is prior to 2.04, the value is
-180˚C.
*2: PL II thermocouple is a range, which has been added
to the units manufactured from July, 2003.
●
PV input range table (DC voltage/DC current)
Handling Precautions
• When the C01 PV input range number is set, the decimal point position
and range are initially set automatically as shown in the tables. For
details on the decimal point, refer to the description of setup C04
(decimal point position) on page 5-4.
• For details about the accuracy of each PV range type, refer to;
Chapter 13, SPECIFICATIONS (on page 13-1).
5-2
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
C01
Sensor
Range
Range
C04
C04
C04 initial value
set value
type
(Celsius)
(Fahrenheit)
display
range
when C01 settings
1
K
-200 to +1200˚C -300 to + 2200˚F
----
(Not setting) (No decimal point)
2
K
0 to 1200˚C
0 to 2200˚F
----
(Not setting) (No decimal point)
3
K
0.0 to 800.0˚C
0 to 1500˚F
----
(Not setting) (No decimal point)
4
K
0.0 to 600.0˚C
0 to 1100˚F
----
(Not setting) (No decimal point)
5
K
0.0 to 400.0˚C
0 to 700˚F
----
(Not setting) (No decimal point)
6
K
-200.0 to +400.0˚C -300 to + 700˚F
----
(Not setting) (No decimal point)
7
K
-200.0 to +200.0˚C -300 to + 400˚F
----
(Not setting) (No decimal point)
9
J
0.0 to 800.0˚C
0 to 1500˚F
----
(Not setting) (No decimal point)
10
J
0.0 to 600.0˚C
0 to 1100˚F
----
(Not setting) (No decimal point)
11
J
-200.0 to +400.0˚C -300 to + 700˚F
----
(Not setting) (No decimal point)
13
E
0.0 to 600.0˚C
0 to 1100˚F
----
(Not setting) (No decimal point)
14
T
-200.0 to +400.0˚C -300 to + 700˚F
----
(Not setting) (No decimal point)
15
R
0 to 1600˚C
0 to 3000˚F
----
(Not setting) (No decimal point)
16
S
0 to 1600˚C
0 to 3000˚F
----
(Not setting) (No decimal point)
17
B
0 to 1800˚C
0 to 3300˚F
----
(Not setting) (No decimal point)
18
N
0 to 1300˚C
0 to 2300˚F
----
(Not setting) (No decimal point)
19
PL II
0 to 1300˚C
0 to 2300˚F
----
(Not setting) (No decimal point)
20
WRe5-26
0 to 1400˚C
0 to 2400˚F
----
(Not setting) (No decimal point)
21
WRe5-26
0 to 2300˚C
0 to 4200˚F
----
(Not setting) (No decimal point)
24
DIN U -200.0 to +400.0˚C -300 to + 700˚F
----
(Not setting) (No decimal point)
25
DIN L
-100.0 to +800.0˚C -150 to + 1500˚F
----
(Not setting) (No decimal point)
C01
Sensor type
Range (C05, C06)
C04
C04
C04 initial value
set value
display range when C01 settings
84
0 to 1V
• Scaling range is -1999 to +9999.
❍
0 to 3
No change
86
1 to 5V
• When C01 is changed, the range (C05, C06)
❍
0 to 3
No change
87
0 to 5V
default defaults to 0 to 1000.
❍
0 to 3
No change
88
0 to 10V
❍
0 to 3
No change
89
0 to 20mA
❍
0 to 3
No change
90
4 to 20mA
❍
0 to 3
No change
C01
Sensor
Range
Range
C04
C04
C04 initial value
set value
type
(Celsius)
(Fahrenheit)
display
range
when C01 settings
41
Pt100
-200.0 to +500.0˚C -300 to + 900˚F
----
(Not setting) (No decimal point)
42
JPt100 -200.0 to +500.0˚C -300 to + 900˚F
----
(Not setting) (No decimal point)
43
Pt100
-200.0 to +200.0˚C -300 to + 400˚F
----
(Not setting) (No decimal point)
44
JPt100 -200.0 to +200.0˚C -300 to + 400˚F
----
(Not setting) (No decimal point)
45
Pt100
-100.0 to +300.0˚C -150 to + 500˚F
----
(Not setting) (No decimal point)
46
JPt100 -100.0 to +300.0˚C -150 to + 500˚F
----
(Not setting) (No decimal point)
51
Pt100
-50.0 to +200.0˚C
-50 to + 400˚F
❍
0 to 1
1
52
JPt100
-50.0 to +200.0˚C
-50 to + 400˚F
❍
0 to 1
1
53
Pt100
-50.0 to +100.0˚C
-50 to + 200˚F
❍
0 to 1
1
54
JPt100
-50.0 to +100.0˚C
-50 to + 200˚F
❍
0 to 1
1
63
Pt100
0.0 to 200.0˚C
0 to + 400˚F
❍
0 to 1
1
64
JPt100
0.0 to 200.0˚C
0 to + 400˚F
❍
0 to 1
1
67
Pt100
0.0 to 500.0˚C
0 to + 900˚F
----
(Not setting) (No decimal point)
68
JPt100
0.0 to 500.0˚C
0 to + 900˚F
----
(Not setting) (No decimal point)