Extended tuning bank, Bank selection – Nor-Cal SDC15 Controller User Manual
Page 141
6-7
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
■
Extended tuning bank
Bank selection:
Display
Item
Contents
Initial
value
User
level
Remarks
AT type
0: Normal (Standard control
characteristics)
1: Immediate response (Control
characteristics that respond
immediately to external
disturbance.)
2: Stable (Control characteristics
having less up/down fluctuation of
PV)
1
0
Displayed when the control
method is other than the
ON/OFF control (CtrL
≠
0).
Just-FiTTER settling
band
0.00 to 10.00
0.30
2
SP lag constant
0.0 to 999.9
0.0
2
Proportional band
tuning factor at AT
0.00 to 99.99
1.00
2
Integral time adjust
0.00 to 99.99
1.00
2
AT Derivative time
adjust
0.00 to 99.99
1.00
2
Control algorithm
0: PID (Conventional PID)
1: Ra-PID (High-performance PID)
0
1
Just-FiTTER
overshoot
suppression factor
0 to 100
0
1
ST (Self-tuning) step
execution resolution
band
0.00 to 99.99
10.00
2
Displayed when the control
method is other than the
ON/OFF control (CtrL
≠
0) and
the control method is ST
(CtrL = 2).
ST (Self-tuning) step
settling band
0.00 to 10.00
0.50
2
ST (Self-tuning)
hunting settling band
0.00 to 10.00
1.00
2
ST (Self-tuning)
step ramp change
0: ST is executed when the PV
moves up or down.
1: ST is executed only when the PV
moves up.
0
1