Nor-Cal SDC15 Controller User Manual
Page 155
6-21
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
Display
Item
Contents
Initial
value
User
level
Remarks
Event output 1
Operation type
Same as Control output 1 Operation
type.
0: Default output
1: MV1
2: MV2
3 to 6: Function 1 to 4
0
2
Event output 1
Output assign A
Same as Control output 1 Output
assign A to D.
0 to 49
2
2
Event output 2
Operation type
Same as Control output 1 Operation
type.
0: Default output
1: MV1
2: MV2
3 to 6: Function 1 to 4
0
2
Displayed when the optional
model has Event output 2.
When using Event output 2,
the default output is Internal
Event 2.
Event output 1
Output assign B
0
2
Event output 1
Output assign C
0
2
Event output 1
Output assign D
0
2
Event output 1
Polarity A to D
1st digit: Polarity A
2nd digit: Polarity B
3rd digit: Polarity C
4th digit: Polarity D
0000
2
Event output 1
Polarity
0: Direct
1: Reverse
0
2
Event output 1
Latch
0: None
1: Latch (Latch at ON)
2: Latch (Latch at OFF except for
initialization at power ON)
0
2
Displayed when the optional
model has Event output 1.
When using Event output 1,
the default output is Internal
Event 1.
Displayed when the optional
model has Event output 1
and the operation type of
Event output 1 is function 1
to 4 (Ev1.1 > 2).
Same as Control output 1 Polarity A
to D.
The following setting applies to each
digit:
0: Direct
1: Reverse
Event output 2
Output assign A
Same as Control output 1 Output
assign A to D.
0 to 49
3
2
Displayed when the optional
model has Event output 2
and the operation type of
Event output 2 is function 1
to 4 (Ev2.1 > 2).
Event output 2
Output assign B
0
2
Event output 2
Output assign C
0
2
Event output 2
Output assign D
0
2
Event output 2
Polarity A to D
1st digit: Polarity A
2nd digit: Polarity B
3rd digit: Polarity C
4th digit: Polarity D
Same as Control output 1 Polarity A
to D.
The following setting applies to each
digit:
0: Direct
1: Reverse
0000
2
Event output 2
Polarity
0: Direct
1: Reverse
0
2
Event output 2
Latch
0: None
1: Latch (Latch at ON)
2: Latch (Latch at OFF except for
initialization at power ON)
0
2