Page 57: 5 - 2 mode
5 - 2
Mode
It is possible to set the AUTO/MANUAL mode selection, RUN/READY mode selection, AT (Auto Tuning)
stop/start selection, release all DO (digital output) latches, and OFF/ON selection of communication DI (digital
input) 1.
■
AUTO/MANUAL mode
The AUTO/MANUAL mode selection can be set.
• When the AUTO/MANUAL mode is changed, the display is automatically
returned to the operation display.
• If the operation type of internal contacts 1 to 3 is set at “AUTO/MANUAL”, [A--
M: AUTO/MANUAL] can be displayed, but the setting cannot be made.
• When [CtrL: Control method] is set at "0" (ON/OFF control), [A--M:
AUTO/MANUAL] cannot be displayed and set.
• When [bit 0: AUTO/MANUAL display] of [C73: MODE display setup] is set at
"0" (no display), [A--M: AUTO/MANUAL] cannot be displayed and set.
■
RUN/READY mode
The RUN/READY mode selection can be set.
• If the operation type of internal contacts 1 to 3 is set at “RUN/READY”, [r--r:
RUN/READY] can be displayed, but the setting cannot be made.
• When [bit 1: RUN/READY display] of [C73: MODE display setup] is set at "0"
(no display), [r--r: RUN/READY] cannot be displayed and set.
5-7
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Setting display/bank)
Display
Contents
Initial value
User level
AUTO/MANUAL
(Parameter setting/Mode
bank)
AUto: AUTO mode [Communication value is
"0".]
MAn: MANUAL mode [Communication value
is "1".]
AUto
Simple,
Standard,
High function
Item (Setting display/bank)
Display
Contents
Initial value
User level
RUN/READY
(Parameter setting/Mode
bank)
rUn: RUN mode [Communication value is "0".]
rdy: READY mode [Communication value is
"1".]
rUn
Simple,
Standard,
High function