Ct display setup, User level, Communication monitor display – Nor-Cal SDC15 Controller User Manual
Page 128
5-78
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
■
CT display setup
Whether or not the CT current value is displayed in the operation display mode
can be set.
• When the optional model has two CT input points, the display and setting can be
made.
■
User level
The user level of the console display can be set.
As a larger value is set, the number of possible displays/settings is increased.
■
Communication monitor display
The function of the decimal point LED at the right end digit of the lower display
(lower 4-digit display) can be set.
Item (Setting display/bank)
Display
Contents
Initial value
User level
CT display setup
(Setup setting/Setup bank)
0: CT current value is not displayed in the
operation display mode.
1: CT1 current value is displayed in the
operation display mode.
2: CT1 to 2 current values are displayed in the
operation display mode.
1
Standard,
High function
Item (Setting display/bank)
Display
Contents
Initial value
User level
User level
(Setup setting/Setup bank)
0: Simple configuration
1: Standard configuration
2: High function configuration
0
Simple,
Standard,
High function
Item (Setting display/bank)
Display
Contents
Initial value
User level
Communication monitor
display
(Setup setting/Setup bank)
0: Disabled
1: Flashing while data is sending through RS-
485 communication.
2: Flashing while data is receiving through RS-
485 communication.
3: Logical OR of all DI statuses
4: Flashing in READY mode
0
High function