Command type, Other specifications – Nor-Cal SDC15 Controller User Manual
Page 180

• 1-frame end judgment
A message end (1-frame end) is determined when a time period specified for
each transmission speed has passed during which no character is received. It is
considered that 1 frame has ended when the next character is not received before
the time-out time shown below passes.
However, the time-out time has a fluctuation of ±1 ms from the values in the
table below.
■ Command type
There are two command (send message) types as shown below:
■ Other specifications
• Supporting the MODBUS Class 0
• Abnormal termination codes
• Maximum number of communications data words
• Other
For the details of MODBUS specifications,
refer to
OPEN MODBUS/TCP SPECIFICATION (Release 1.0) by
Modicon Inc.
8-6
Chapter 8. MODBUS COMMUNICATIONS FUNCTIONS
Set transmission speed
Time-out time
(bps)
4800
16ms or more
9600
8ms or more
19200
4ms or more
38400
2ms or more
Command
Description
ASCII
RTU (binary)
Read command
"03" (sample)
03H (sample)
Write command
"10" (sample)
10H (sample)
Code
Description
01
Command error
02
Address error
03
Data error
Data count
ASCII
RTU
03 (READ)
16
16
16 (WRITE)
16
16