Chapter 6. LIST OF DISPLAYS AND SETTING DATA

Display

Item

Contents

Initial
value

User
level

Remarks

Timer remain time
display setup

0: ON/OFF delay remain time of

Internal Event is not displayed in
the operation display mode.

1: ON/OFF delay remain time of

Internal Event 1 is displayed in the
operation display mode.

2: ON/OFF delay remain time of

Internal Events 1 to 2 is displayed
in the operation display mode.

3: ON/OFF delay remain time of

Internal Events 1 to 3 is displayed
in the operation display mode.

0

1

CT display setup

0: CT current value is not displayed

in the operation display mode.

1: CT1 current value is displayed in

the operation display mode.

2: CT1 to 2 current values are

displayed in the operation display
mode.

0

1

User level

0: Simple configuration
1: Standard configuration
2: High function configuration

0

0

Communication
monitor display

0: Not used.
1: Flashing while data is sending

through RS-485 communication.

2: Flashing while data is receiving

through RS-485 communication.

3: Logical OR of all DI statuses
4: Flashing in READY mode

0

2

MV display setup

Whether or not the PV/SP value
related items are displayed in the
basic display mode is determined by
the sum of the following weights:
Bit 0: MV display

Disabled: 0, Enabled: +1

Bit 1: Heat MV/cool MV display

Disabled: 0, Enabled: +2

Bit 3: AT progress display

Disabled: 0, Enabled: +8

Other invalid settings, 0, +4

15

1

EV display setup
(Setup setting/Setup
bank)

0: Internal Event set value is not

displayed in the operation display
mode.

1: Set value of Internal Event 1 is

displayed in the operation display
mode.

2: Set values of Internal Events 1 to 2

are displayed in the operation
display mode.

3: Set values of Internal Events 1 to 3

are displayed in the operation
display mode.

0

1

Handling Precautions

• If ROM version 1 of the instrument information bank(

Id02

) is prior to

2.04, the setting options for [Number of CT1 turns], [Number of CT1
power wire loops], [Number of CT2 turns] and [Number of CT2 power
wire loops] are not displayed.

Number of CT2 power
wire loops

0: 1 time
1 to 6: Number of times

1

2

Number of CT2 turns

0: 800 turns
1 to 40: CT turns devided by 100.

8

2

Number of CT1 turns

0: 800 turns
1 to 40: CT turns devided by 100.

8

2

Number of CT1 power
wire loops

0: 1 times
1 to 6: Number of times

1

2

If the controller model has 2
current transformer inputs,
this setting is displayed.

6-12