Nor-Cal SDC15 Controller User Manual
Page 195
Bank
Item name
RAM address
EEPROM address
RAM
EEPROM
Decimal point
Remarks
Decimal Hexadecimal Decimal Hexadecimal Read Write Read Write information
Operation
LSP group selection
9103
238F
25487
638F
✽
✽
—
Same as RAM address
display
14592 (decimal). Writing is
enabled under no DI
Assignment conditions.
(Note 3)
(Reserved for future extension.)
9104
2390
25488
6390
∆
X
∆
X
—
MV (Manipulated Variable)
9105
2391
25489
6391
✽
✽
1
Same as RAM address
14594 (decimal). Writing is
enabled in the MANUAL
mode.
Heat MV (Manipulated Variable)
9106
2392
25490
6392
X
X
1
Same as RAM address
14420 (decimal).
Cool MV (Manipulated Variable)
9107
2393
25491
6393
X
X
1
Same as RAM address
14421 (decimal).
(Reserved for future extension.)
9108
2394
25492
6394
∆
X
∆
X
1
Same as RAM address
14417 (decimal).
AT progress
9109
2395
25493
6395
X
X
—
CT (Current transformer)
9110
2396
25494
6396
X
X
1
Same as RAM address
current value 1
14418 (decimal).
CT (Current transformer)
9111
2397
25495
6397
X
X
1
Same as RAM address
current value 2
14419 (decimal).
Timer remain time 1
9112
2398
25496
6398
X
X
S
Timer remain time 2
9113
2399
25497
6399
X
X
S
Timer remain time 3
9114
239A
25498
639A
X
X
S
Timer remain time 4
9115
239B
25499
639B
X
X
S
Timer remain time 5
9116
239C
25500
639C
X
X
S
(Reserved for future extension.)
9117
239D
25501
639D
∆
X
∆
X
S
(Reserved for future extension.)
9118
239E
25502
639E
∆
X
∆
X
S
(Reserved for future extension.)
9119
239F
25503
639F
∆
X
∆
X
S
(Reserved for future extension.)
9120
23A0
25504
63A0
∆
X
∆
X
S
(Reserved for future extension.)
9121
23A1
25505
63A1
∆
X
∆
X
S
(Reserved for future extension.)
9122
23A2
25506
63A2
∆
X
∆
X
S
LSP value in use
9123
23A3
25507
63A3
P
Same as RAM address
14593 (decimal). (Note 2)
PV before ratio, bias, and filter
9124
23A4
25508
63A4
X
X
P
(Reserved for future extension.)
9125
23A5
25509
63A5
∆
X
∆
X
P
Status
Input alarm status
9201
23F1
25585
63F1
X
X
—
Bit 0: AL01 (PV over-range)
Bit 1: AL01 (PV under-
range)
Bit 2: AL03 (CJ, RTD
burnout)
Bits 3 to 15: Undefined.
Instrument alarm status
9202
23F2
25586
63F2
X
X
—
Bits 0 to 1: Undefined.
Bit 2: AL70 (A/D)
Bit 3: AL95 (Set data)
Bit 4: AL96 (Adjustment
data)
Bit 5: AL97 (Set data/RAM)
Bit 6: AL98 (Adjustment
data/RAM)
Bit 7: AL99 (ROM)
Bits 8 to 15 Undefined.
9-9
Chapter 9. LIST OF COMMUNICATION DATA
(Note 2) If the value is read immediately after it has been written into the SP or the LSP in use, the value still may
not be changed. The value is updated after the cycle time has elapsed.
(Note 3) If the SP or the LSP in use is read immediately after the value has been written into the LSP group
selection, the value still may not be changed. The value is updated after the cycle time has elapsed.