Nor-Cal SDC15 Controller User Manual
Page 144

6-10
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
Display
Item
Contents
Initial
value
User
level
Remarks
Control output 1
range
1: 4 to 20mA
2: 0 to 20mA
1
0
Displayed when control
output 1 of the model is the
current output.
The decimal point position of
the scaling low limit/high limit
becomes 1 digit after the
decimal point when the
control output 1 type is
related to the MV and CT.
When the control output 1
type is related to the PV and
SP, the decimal point
position becomes the same
as that of the PV.
Control output 1 type
0: MV
1: Heat MV (for heat/cool control)
2: Cool MV (for heat/cool control)
3: PV
4: PV before ratio, bias, and filter
5: SP
6: Deviation
7: CT1 current value
8: CT2 current value
9: MFB (Invalid on SDC15)
10: SP+MV
11: PV+MV
0
0
Control output 1
scaling low limit
-1999 to +9999
The decimal point position may vary
depending on control output 1 type
(C43).
0
0
Control output 2
range
1: 4 to 20mA
2: 0 to 20mA
1
0
Control output 2 type
0: MV
1: Heat MV (for heat/cool control)
2: Cool MV (for heat/cool control)
3: PV
4: PV before ratio, bias, and filter
5: SP
6: Deviation
7: CT1 current value
8: CT2 current value
9: MFB (Invalid on SDC15)
3
0
Control output 2
scaling low limit
-1999 to +9999
The decimal point position may vary
depending on control output 2 type
(C48).
0
0
Displayed when control
output 2 of the model is the
current output.
The decimal point position of
the scaling low limit/high limit
becomes 1 digit after the
decimal point when the
control output 2 type is
related to the MV and CT.
When the control output 2
type is related to the PV and
SP, the decimal point
position becomes the same
as that of the PV.
Control output 2
scaling high limit
1000
0
Control output 1
scaling high limit
100.0
0
Control output 1 MV
scaling
200.0
0
0 to 9999
The decimal point position and unit
are same as for PV.
If the controller model uses
current output for control
output 1 and if the control
output 1 type is SP+MV or
PV+MV, this setting is
displayed.
Control output 2 MV
scaling
200.0
0
0 to 9999
The decimal point position and unit
are same as for PV.
If the controller model uses
current output for control
output 2 and if the control
output 2 type is SP+MV or
PV+MV, this setting is
displayed.
Handling Precautions
• If ROM version 1 of the instrument information bank(
Id02
) is prior to
2.04, SP+MV and PV+MV cannot be set in [Control output 1 type],
[Control output 2 type], and [Auxiliary output type ].
• If ROM version 1 of the instrument information bank(
Id02
) is prior to
2.04, SP+MV and PV+MV cannot be set in [Control output 1 MV
scaling], [Control output 2 MV scaling], and [Auxiliary output MV
scaling ].