Nor-Cal SDC15 Controller User Manual
Page 143
6-9
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
Display
Item
Contents
Initial
value
User
level
Remarks
Output operation at
changing Auto/Manual
0: Bumpless transfer
1: Preset
0
1
Displayed when the control
method is other than the
ON/OFF control (CtrL≠0).
When the operation mode is
the MANUAL mode at power
ON, the preset MANUAL
value (C20) becomes the
Manipulated Variable (MV).
Preset MANUAL
value
-10.0 to +110.0%
0.0 or
50.0
1
Initial output type
(mode) of PID control
0: Auto
1: Not initialized.
2: Initialized (If SP value different
from the current value is input.)
0
2
Initial output of PID
control
-10.0 to +110.0%
0.0 or
50.0
2
Heat/Cool control
0: Not used.
1: Used.
0
0
Displayed when the control
method is other than the
ON/OFF control (CtrL≠0).
When set at “1”, the control
action is set to the reverse
action (C14 = 0), the preset
MANUAL value (C20) is set
to “50.0”, and the initial
output of the PID control
(C22) is changed to “50.0”.
Heat/Cool selection
0: Normal
1: Energy saving
0
1
Heat/Cool control
dead zone
-100.0 to +100.0%
0.0
0
Heat/Cool control
change point
-10.0 to +110.0%
50.0
2
LSP system group
1 to 4
1
0
SP ramp unit
0: 0.1U/s
1: 0.1U/min
2: 0.1U/h
1
2
"0.1U" shows that the
decimal point position of the
PV is shifted one digit
rightward.
Displayed when the
Heat/Cool control is used
(C26 = 1).
CT1 operation type
0: Heater burnout detection
1: Current value measurement
0
0
Displayed when the optional
model has two current
transformer input points.
CT1 output
0: Control output 1
1: Control output 2
2: Event output 1
3: Event output 2
4: Event output 3
0
0
Displayed when the optional
model has two current
transformer input points and
the CT1 operation type is set
at "heater burnout detection"
(C36 = 0).
CT1 measurement
wait time
30 to 300ms
30
0
CT2 operation type
Same as CT1
0
0
Displayed when the optional
model has two current
transformer input points.
CT2 output
Same as CT1
0
0
Displayed when the optional
model has two current
transformer input points and
the CT2 operation type is set
at "heater burnout detection"
(C39 = 0).
CT2 measurement
wait time
Same as CT1
30
0