Pid bank, Bank selection – Nor-Cal SDC15 Controller User Manual
Page 139
6-5
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
■
PID bank
Bank selection:
Display
Item
Contents
Initial
value
User
level
Remarks
P (Proportional band)
0.1 to 999.9%
5.0
0
MV low limit
0.0
1
Displayed when the control
method is other than the
ON/OFF control (CtrL
≠
0).
-10.0 to +110.0%
Displayed when the control
method is other than the
ON/OFF control (CtrL
≠
0).
P (Proportional band)
(cool)
5.0
0
0.1 to 999.9%
Displayed when the control
method is other than the
ON/OFF control (CtrL
≠
0) and
the Heat/Cool control is used
(C26 = 1).
I (Integral time)
(cool)
120
0
0 to 9999s
(No integration control action when
set at "0".)
D (Derivative time)
(cool)
30
0
0 to 9999s
(No derivative control action when
set at "0".)
I (Integral time)
0 to 9999s
(No integration control action when
set at "0".)
120
0
D (Derivative time)
0 to 9999s
(No derivative control action when
set at "0".)
30
0
Manual reset
-10.0 to +110.0%
50.0
0
Displayed when the control
method is other than the
ON/OFF control (CtrL
≠
0) and
the I (Integral time) (I-1) is
“0”.
MV high limit
100.0
1
-10.0 to +110.0%
Output low limit (Cool)
0.0
1
-10.0 to +110.0%
Output high limit
(Cool)
100.0
1
-10.0 to +110.0%