Chapter 13. specifications, Specifications – Nor-Cal SDC15 Controller User Manual
Page 209
Chapter 13. SPECIFICATIONS
13-1
■
Specifications
●
PV input
Input type:
Thermocouple K, J, E, T, R, S, B, N (JIS C1602-1995)
PL II (Engelhard Industries data(ITS90))
WRe5-26 (ASTM E988-96(Reapproved 2002))
DIN U, DIN L (DIN43710-1985)
RTD Pt100 (JIS C1604-1997), JPt100 (JIS C1604-1989)
DC voltage 0 to 1Vdc, 1 to 5Vdc, 0 to 5Vdc, 0 to 10Vdc
DC current 0 to 20mAdc, 4 to 20mAdc
Sampling cycle time: 500ms
Indication accuracy:
±0.5%FS±1 digit, ±1%FS±1digit in the negative area of the thermocouple
(Specified by the input conversion at an ambient temperature of 23±2˚C)
However, the accuracy of the B-thermocouple is ±5%FS at a temperature
of 260˚C or less and ±1%FS at a temperature of 260 to 800˚C.
The low limit for indication is 20˚C. However, if ROM version 1 of the
instrument information bank (Id02) is prior to 2.04, the low limit for
indication is -180˚C.
PV bias:
-1999 to +9999 or -199.9 to +999.9
• Thermocouple (T/C) input
Input bias current:
+0.2µA (Flowed from the A terminal.)
Burnout indication:
Upscale + AL01
Thermocouple or
compensating wire:
0.3 to 0.65mm diameter
• Resistance temperature detector (RTD) input
Input bias current:
Approx. +1mA (Flowed from the A terminal.)
Burnout indication:
RTD burnout or A-wire burnout . . . . . Upscale + AL01
B-wire burnout or C-wire burnout . . . . Upscale + AL01, AL03
2 or more wires burnout . . . . . . . . . . . . Upscale + AL01, AL03
Allowable wiring
resistance:
Max. 10Ω at range No.51 to 64, max. 85Ω the other ranges.
Influence of wiring
resistance:
Max. ±0.05% FS/Ω Max. 10Ω at range No.51 to 64, max. 85Ω the other
ranges.
• DC voltage input
Input impedance:
Min. 1MΩ
Input bias current:
0 to 1V range . . . . . . . . . . . . . . . . . . . .1µA (sucked to the A terminal)
0 to 5V, 1 to 5V range . . . . . . . . . . . . .3.5µA (sucked to the A terminal)
0 to 10V range . . . . . . . . . . . . . . . . . . .7µA (sucked to the A terminal)
Burnout indication:
Downscale + AL02
However, the burnout cannot be detected in a range of 0 to 10V.
• DC current input
Input impedance:
Max. 100Ω
Burnout indication:
Downscale + AL02
However, the burnout cannot be detected in a range of 0 to 20mA.
Allowable input
current:
Max. 30mA