Direct/reverse, standby, and EVENT state at READY

Direct/reverse, standby, and EVENT state at READY accompanying with the

operation type can be set.

• When the internal event configuration 1 operation type is set at [0: No event], the

internal event configuration 2 (direct/reverse, standby, and EVENT state at

READY) is not displayed.

• For details about internal event operation with the direct/reverse setting,

refer to the

List of internal event operations (on pages 5-39 to 5-44)

.

Handling Precautions

• “Standby” is a function that does not turn ON the event even though

the event currently used satisfies the ON conditions (before polarity)

when the instrument power is turned ON or when the READY mode is

changed to the RUN mode. The event is turned ON when the ON

conditions are satisfied again once the OFF conditions have been

satisfied.

• “Standby + Standby at SP change” means that the standby is set

again when the SP is changed (SP value and LSP group number) in

addition to the standby functions. However, when the same SP value

is written or when the SP value is not changed even though the LSP

group number is changed, the unit does not enter the standby mode.

EVENT state at 0:Continued

1: Forced OFF 0: Continued

1: Forced OFF

READY setup

Standby setup

0: None

Usual operation OFF

Usual operation

Usual operation

1: Standby

OFF

OFF

OFF(standby state) OFF(standby state)

2: Standby+

OFF

OFF

OFF(standby state) OFF(standby state)

Standby at SP change

READY

READY RUN change

5-46

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Internal Event 1
Configuration 2 Operation type
(Setup setting/Event
Configuration bank)

The digits are called 1st digit, 2nd digit, 3rd
digit, and 4th digit from the right end.
1st digit: Direct/reverse setup

0:

Direct

1:

Reverse

2nd digit: Standby setup

0:

None

1:

Standby

2:

Standby + Standby at SP change

3rd digit: EVENT state at READY setup

0:

Continued.

1:

Forced OFF

4th digit: Undefined.

0:

Undefined.

0000

Simple,
Standard,
High function

0000

Internal Event 2
Configuration 2 Operation type
(Setup setting/Event
Configuration bank)

0000

Internal Event 3
Configuration 2 Operation type
(Setup setting/Event
Configuration bank)

0000

Internal Event 4
Configuration 2 Operation type
(Setup setting/Event
Configuration bank)

0000

Internal Event 5
Configuration 2 Operation type
(Setup setting/Event
Configuration bank)