Direct/reverse, standby, and EVENT state at READY
Direct/reverse, standby, and EVENT state at READY accompanying with the
operation type can be set.
• When the internal event configuration 1 operation type is set at [0: No event], the
internal event configuration 2 (direct/reverse, standby, and EVENT state at
READY) is not displayed.
• For details about internal event operation with the direct/reverse setting,
List of internal event operations (on pages 5-39 to 5-44)
Handling Precautions
• “Standby” is a function that does not turn ON the event even though
the event currently used satisfies the ON conditions (before polarity)
when the instrument power is turned ON or when the READY mode is
changed to the RUN mode. The event is turned ON when the ON
conditions are satisfied again once the OFF conditions have been
satisfied.
• “Standby + Standby at SP change” means that the standby is set
again when the SP is changed (SP value and LSP group number) in
addition to the standby functions. However, when the same SP value
is written or when the SP value is not changed even though the LSP
group number is changed, the unit does not enter the standby mode.
EVENT state at 0:Continued
1: Forced OFF 0: Continued
1: Forced OFF
READY setup
Standby setup
0: None
Usual operation OFF
Usual operation
Usual operation
1: Standby
OFF
OFF
OFF(standby state) OFF(standby state)
2: Standby+
OFF
OFF
OFF(standby state) OFF(standby state)
Standby at SP change
READY
READY RUN change
5-46
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Setting display/bank)
Display
Contents
Initial value
User level
Internal Event 1
Configuration 2 Operation type
(Setup setting/Event
Configuration bank)
The digits are called 1st digit, 2nd digit, 3rd
digit, and 4th digit from the right end.
1st digit: Direct/reverse setup
0:
Direct
1:
Reverse
2nd digit: Standby setup
0:
None
1:
Standby
2:
Standby + Standby at SP change
3rd digit: EVENT state at READY setup
0:
Continued.
1:
Forced OFF
4th digit: Undefined.
0:
Undefined.
0000
Simple,
Standard,
High function
0000
Internal Event 2
Configuration 2 Operation type
(Setup setting/Event
Configuration bank)
0000
Internal Event 3
Configuration 2 Operation type
(Setup setting/Event
Configuration bank)
0000
Internal Event 4
Configuration 2 Operation type
(Setup setting/Event
Configuration bank)
0000
Internal Event 5
Configuration 2 Operation type
(Setup setting/Event
Configuration bank)