Nor-Cal SDC15 Controller User Manual
Page 114
◆
Setting example
• Event
Note. The internal event No. is indicated at the mark of "x" shown in the Display
column.
• DI Assignment
Note. The internal DI No. is indicated at the mark of "x" shown in the Display
column.
5-64
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Event
Display
Internal Event 1
Internal Event 2
Operation type
Ex.C1
9: Deviation high/low limit
32: Timer (Status)
(Final SP reference)
Direct/reverse
Ex.C2
1: Reversed.
----
Standby
Ex.C2
0: No standby
----
EVENT state at READY
Ex.C2
1: EVENT state at READY
0: EVENT state at READY
is forcibly turned OFF.
is continued.
Alarm OR
Ex.C3
0: None
0: None
Special OFF setup
Ex.C3
0: As usual.
----
Delay time unit
Ex.C3
0: 0.1s
0: 0.1s
Event main setting
Ex
3
----
(low limit)
Event sub setting
Ex.SB
3
----
(high limit)
Hysteresis
Ex.HY
9999
----
ON delay
Ex.ON
2
15
OFF delay
Ex.OF
0
0
DI Assignment
Display
Internal Contact 1
Internal Contact 2
Operation type
DIx.1
7: RUN/READY
17: Timer stop/start
Input bit function
DIx.2
1: Function 1 (A and B) or
1: Function 1 (A and B) or
(C and D)
(C and D)
Input assign A
DIx.3
18: COM DI 1
10: Internal Event 1
(Setting = 9: Deviation
high/low limit (Final SP
reference)
Input assign B
DIx.4
11: Internal Event 2
26: During SP ramp
(Setting = 32: Timer
(Status))
Input assign C
DIx.5
0: Normally opened.
18: COM DI 1
(Normally Off = 0)
Input assign D
DIx.6
0: Normally opened.
11: Internal Event 2
(Normally Off = 0)
(Setting = 32:
Timer (Status))
Polarity A
DIx.7
0: Direct
0: Direct
Polarity B
DIx.7
1: Reverse
1: Reverse
Polarity C
DIx.7
0: Direct
0: Direct
Polarity D
DIx.7
0: Direct
0: Direct
Polarity
DIx.8
1: Reverse
0: Direct
Event channel def.
DIx.9
----
2