Nor-Cal SDC15 Controller User Manual
Page 148
6-14
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
Display
Item
Contents
Initial
value
User
level
Remarks
Internal Event
Configuration 3
The digits are determined to 1st digit,
2nd digit, 3rd digit, and 4th digit from
the right end.
0000
2
4th digit: Undefined.
0
1st digit: Controller
alarm OR
0: None
1: Alarm direct + OR operation
2: Alarm direct + AND operation
3: Alarm reverse + OR operation
4: Alarm reverse + AND operation
2nd digit: Special OFF
setup
0: As usual.
1: When the event set value (main
setting) is “0”, the event is “OFF”.
3rd digit: Delay unit
0: 0.1s
1: 1s
2: 1min
Internal Event 2
Configuration 1
Operation type
Same as Internal Event 1
Configuration 1.
0
0
Internal Event 2
Configuration 2
1st digit: Direct/
Reverse
2nd digit: Standby
3rd digit: EVENT state
at READY
4th digit: Undefined.
Same as Internal Event 1
Configuration 2.
0000
0
Internal Event 2
Configuration 3
1st digit: Controller
alarm OR
2nd digit: Special OFF
setup
3rd digit: Delay unit
4th digit: Undefined.
Same as Internal Event 1
Configuration 3.
0000
2
Internal Event 3
Configuration 1
Operation type
Same as Internal Event 1
Configuration 1.
0
0
Internal Event 3
Configuration 2
1st digit: Direct/
Reverse
2nd digit: Standby
3rd digit: EVENT state
at READY
4th digit: Undefined.
Same as Internal Event 1
Configuration 2.
0000
0
Internal Event 3
Configuration 3
1st digit: Controller
alarm OR
2nd digit: Special OFF
setup
3rd digit: Delay unit
4th digit: Undefined.
Same as Internal Event 1
Configuration 3.
0000
2
Internal Event 4
Configuration 1
Operation type
Same as Internal Event 1
Configuration 1.
0
0
Internal Event 4
Configuration 2
1st digit: Direct/
Reverse
2nd digit: Standby
3rd digit: EVENT state
at READY
4th digit: Undefined.
Same as Internal Event 1
Configuration 2.
0000
2