9 internal event, 5 - 9 internal event – Nor-Cal SDC15 Controller User Manual
Page 88
5 - 9
Internal Event
5-38
The result of the internal event process can be output to the control output or event output through the DO (digital
output) process.
For details,
2-1, Input/Output Configuration (on page 2-1)
The following shows the functional block diagram of the internal event:
Handling Precautions
Even though five internal events 1 to 5 are provided, the number of event
outputs determined by the optional model is 0 to 3 points. With the default
settings before shipment, the operations of internal events 1 to 3 can be
output to event outputs 1 to 3. To utilize the operations of internal events 4
to 5, it is absolutely necessary to set the DO Assignment.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Operation type
(Setting: Event Configuration
Operation type E1. C1 to E5. C1)
Direct/reverse, Standby
(Setting: Event Configuration,
Direct/reverse, Standby E1. C2 to E5. C2)
Controller alarm OR/AND
(Setting: Event Configuration
E1.C3 to E5.C3)
EVENT state at READY
(Setting: Event Configuration
E1.C2 to E5.C2)
Main setting, sub setting,
hysteresis, special OFF setup
(Setting: Event E1 to E5, E1.SB to E5.SB,
E1.HY to E5.HY, E1. Event Configuration
E1.C3 to E5.C3)
ON delay, OFF delay, Delay time unit
(Setting: Event E1.ON to E5.OF,
E1.OF to E5.OF, E1.
Event Configuration E1.C3 to E5.C3)
Internal Event status