Operation in case of pv input failure, Refer to – Nor-Cal SDC15 Controller User Manual
Page 200

■
Operation in case of PV input failure
(1) AL01, 02, or 03 occurs.
Control output: It is possible to make the settings so that the operation is
continued or not continued.
Other operation: Operation is continued.
(2) AL occurs in cases other than those shown above.
All operations are continued.
The following Table shows the indications and alarms of this unit by the sensor
type if PV input failure occurs:
●
Thermocouple
●
RTD
●
DC voltage/DC current
10-2
Chapter 10. MAINTENANCE AND TROUBLESHOOTING
Failure status
Range No.
Indication value
Alarm code
Burnout
84 (0 to 1V)
Downscale (-3%FS)
AL02
86 (1 to 5V)
Downscale (-10%FS)
AL02
87 (0 to 5V)
Downscale (-3%FS)
AL02
88 (0 to 10V)
Downscale (0%FS)
None
89 (0 to 20mA)
Unknown (around 0%FS)
None
90 (4 to 20mA)
Downscale (-10%FS)
AL02
Failure status
Range No.
Indication value
Alarm code
Sensor burnout
Upscale (110%FS)
AL01
CJ failure
PV having incorrect cold
AL03
contact compensation
Over-range, burnout
19 (PLII)
1365˚C (105%FS)
AL01
Failure status
Range No.
Indication value
Alarm code
RTD burnout
Upscale (110%FS)
AL01
A-wire burnout
Upscale (110%FS)
AL01
B-wire burnout
Upscale (110%FS)
AL01, AL03
C-wire burnout
Upscale (110%FS)
AL01, AL03
2- or 3-wire burnout
Upscale (110%FS)
AL01, AL03
A- and B-wire short-circuit
Downscale (-10%FS)
AL02
A- and C-wire short-circuit
Downscale (-10%FS)
AL02
A- and B-wire/A- and
41 (Pt100)
-235˚C (-5%FS)
AL02
C-wire short-circuit
A- and B-wire/A- and
42 (JPt100)
-235˚C (-5%FS)
AL02
C-wire short-circuit