0 maintenance and service (cont’d), 2 maintenance procedures (cont’d), 5 heat pump maintenance (cont’d) – Reznor ZQYRA Unit Installation Manual User Manual
Page 66

Form I-ZQYRA P/N 260414R5, Page 66
Refrigerant Charge and Check - The unit is factory charged and should require no further adjustment at startup.
Follow these steps to check the refrigerant charge.
NOTE: System charging is not recommended below 70°F (21°C).
1. Attach gauge manifolds and operate the unit in test mode.
2. Set the unit to its nominal airflow (Paragraph 9.3.1).
ZQYRA-8: 800 cfm supply and 1600 cfm exhaust
ZQYRA-12: 1200 cfm supply and 2400 cfm exhaust
3. Turn the wheel off and run the unit in cooling mode until
system stabilizes (approximately 5 minutes).
4. Compare the normal operating pressures in the tables
(right) to the pressures obtained from the gauges.
Minor variations in these pressures may be expected due
to the differences in installations. Significant differences
could mean that the system is not properly charged or
that a problem exists with some component in the system.
Correct any system problems before proceeding.
5. If discharge pressure is high, remove refrigerant from the
system.
If discharge pressure is low, add refrigerant to the system.
Add or remove charge in small increments. Continue
check until pressures are determined to be correct.
WARNING
Do not release refrigerant to the atmosphere.
When adding or removing refrigerant, the
qualified technician must comply with all
national, state/province, and local laws.
ZQYRA-8
Outside Air
Temperature
(ºF)
Suction
Pressure
±5 psig
Discharge
Pressure
±10 psig
Return Air Temperature is 75ºF
70
86
344
75
93
363
80
100
383
85
108
404
90
117
425
95
126
447
100
136
469
105
147
493
Return Air Temperature is 80ºF
70
87
357
75
94
376
80
101
396
85
109
417
90
118
439
95
127
461
100
137
484
105
148
507
Return Air Temperature is 85ºF
70
88
370
75
95
390
80
102
410
85
110
431
90
118
453
95
128
475
100
138
498
105
149
522
ZQYRA-12
Outside Air
Temperature
(ºF)
Suction
Pressure
±5 psig
Discharge
Pressure
±10 psig
Return Air Temperature is 75ºF
70
104
307
75
111
323
80
119
339
85
128
357
90
138
375
95
148
394
100
159
413
105
171
433
Return Air Temperature is 80ºF
70
105
317
75
112
334
80
121
351
85
129
369
90
139
387
95
149
406
100
160
426
105
173
446
Return Air Temperature is 85ºF
70
106
329
75
113
345
80
121
363
85
130
381
90
140
399
95
151
418
100
162
438
105
174
459
Coils and Tubing - Inspect the coils for debris, dirt, grease, lint, mold, or any element
which would obstruct heat transfer or airflow. Inspect coils and tubing for physical dam-
age. Inspect feeders, piping connections, coil headers, and return bends for signs of
fatigue, rubbing, and physical damage.
To clean the coils, use the proper tools and follow the instructions carefully to avoid
damaging the coil. Use of a non-acid based coil cleaner is recommended. Due to pos-
sible damage to the coil, high pressure spray is not recommended.
Cleaning Instructions:
1. Verify that the electrical power has been turned off and disconnect switch locked.
2. Open the coil cabinet door.
3. Use a soft brush to remove any dirt and debris from both sides of the coil.
4. Spray with cold or warm (not hot) water and a cleaning solution (non-acid based
coil cleaner is recommended). Due to possible damage to the coil, high pressure
spray is not recommended. First spray the leaving airflow side, then the inlet
airflow side. As much as possible, spray the solution perpendicular to the face of
the coil. Follow the instructions on the cleaning solution. When cleaning process is
complete, rinse both sides with cool, clean water.
Condensate Pan and Drain - The combination of airborne particles and moisture
can result in algae formation in the drain pan and trap. The drain pan and trap must
be cleaned regularly to avoid blockage that can slow or stop water flow, resulting in
backup into the cabinet. Clean the drain pan, trap, and piping. After cleaning, re-install
all parts and fill the trap with water to ensure proper operation.
10.0 Maintenance
and Service
(cont’d)
10.2 Maintenance Procedures (cont’d)
10.2.5 Heat Pump Maintenance (cont’d)