beautypg.com

Reznor ZQYRA Unit Installation Manual User Manual

Page 33

background image

Form I-ZQYRA P/N 260414R5, Page 33

Unless noted in the specific sequences below, when a shutdown alarm occurs a man-

ual restart is required to return the unit to normal operation. Manual restart can be done

by resetting the system shutdown alarm from the unit interface module, by cycling

power to the unit, or by restarting through a field-supplied Building Automation System.
Shutdown Digital Input (DI-5) Alarm - Whenever the system controller sees the shut-

down contact go into the alarm condition (open), the controller will initiate a specific

alarm to indicate alarm condition and shut down the unit. The unit will remain off and

in the alarm condition until the shutdown contact alarm condition is cleared (closed).

Once the alarm is cleared, the unit will automatically clear the alarm and restart the

system in normal operation.

Cripple Mode Time Exceeded Alarm - If the unit exceeds the allowed cripple mode

operation time limit, the unit will shut down and will initiate a specific alarm to indicate

alarm condition. The unit mode shows “Shutdown” on the summary page. For more

detailed sequence, see the “Cripple Mode” operation sequence. Once the unit is in

this mode, the unit must be manually restarted. The alarm(s) that caused the system

shutdown will be logged in the alarm screen under the Alarm History Menu.

Multiple Restart Shutdown Alarm - The system is allowed to go through the restart

sequence a fixed number of times over a 24 hour period. Once the unit has gone

through the auto restart limit (

Auto Restart = 3), the system controller locks the sys-

tem out. The unit mode shows “Shutdown” on the summary page. Once the unit is in

this mode, the unit must be manually restarted. The alarm(s) that caused the system

shutdown will be logged in the alarm screen under the Alarm History Menu.

Multiple Sensor Failure - If at any time the unit has multiple sensor failures (sensor

failures are listed under the Cripple Mode Operation Sequence Mode), the unit will

shut down and issue a specific alarm to indicate alarm condition and the unit mode

shows “Shutdown” on the summary page. Once the unit is in this mode, the unit must

be manually restarted. The alarm(s) that caused the system shutdown will either still

be active in the active alarm screen or will be logged in the alarm screen under the

Alarm History Menu.

High Outside Air Temperature Limit Alarm - If the outside air temperature is above

High Outside Air Alarm setpoint (

Hi OAT Setpoint = 115°F/

46°C), the system will shut-

down the unit and initiate a specific alarm. The unit will remain off until the outside air

temperature is below the outside air temperature high lockout setpoint by the High

Outside Air Alarm Deadband (

Hi OAT Deadband = 5°F/3°C)

Wheel Defrost Alarm - The unit has a builtin wheel defrost sequence to prevent dam-

age to the wheel. If the wheel discharge temperature falls below the Energy Recovery

Wheel Discharge Air Temperature (

ERW DAT Limit = 32°F/0°C) and the humidity is

above the Energy Recovery Wheel Discharge Air Humidity (

ERW DAH Limit = 90%)

for more than High Limit Timer (

Limit Timer = 10 minutes), the system shall enable

defrost control.

The first stage of defrost control is to activate the preheat coil (if available). After the

stage one timer (

Stage1Timer = 10 minutes) has elapsed, if the conditions do not

rise above the setpoints, the unit will shutdown. If no preheat is available, the unit will

shutdown. The system will automatically restart after one of the defrost auto reset

conditions are met.

• When the unit has been off for the minimum defrost time (

Time Reset = 6 hours)

• When the outside air temperature rises above the reset temperature (

OAT Reset =

34°F/1°C).

If three alarms occur within a 24 hour period, the unit will lockout and require a manual

restart.

8.3.2 Maintenance

Alarms

Maintenance alarms only provide information that can be used in helping to maintain

the equipment to insure optimum performance. The filter alarm is activated only when

the option is ordered. Run time alarms are built-in to the system but are disabled by

default. They can be enabled through the unit interface under the “Service” / ”Run

Times” menus.
Filter Alarm - The system monitors the filter pressure using a dedicated pressure

switch. Adjusting the switch trip pressure is done manually at the pressure switch (See

Paragraph 8.8.). Upon a switch closure, the system initiates a specific alarm to indicate