Alarm help menu – Reznor ZQYRA Unit Installation Manual User Manual
Page 49

Form I-ZQYRA P/N 260414R5, Page 49
Page 2: (Shown only when Unit DAT Fail is selected)
--Alarm Help--
Unit Discharge Air Temperature sensor has failed. NOTE: Heat
pump will not operate with a failed unit.
↓ More
More Items
Page 3:(Shown only when Unit DAT Fail is selected)
--Alarm Help--
Discharge Air Temp Sensor. Sensor reading of -60 = open circuit
and a reading of 225 = shorted circuit.
↓ More
More Items
Page 4:(Shown only when Unit DAT Fail is selected)
--Alarm Help--
1. Verify sensor wire integrity.
2. Verify sensor resistance (See APPENDIX page 70).
↓ More
More Items
Page 5:(Shown only when Unit DAT Fail is selected)
--Alarm Help--
3. See Paragraph 10.0 for more troubleshooting info.
4. Replace sensor.
5. Contact technical support: 800-695-1901
↓ Menu Top
Returns to the top of the menu (Page 2)
Press the Esc button to go Menu page 1
Page 2:(Shown only when OAT Fail is selected)
--Alarm Help--
The Outside Air Temperature sensor has failed. Sensor reading
of -60 = open circuit and a reading of 225 = shorted circuit.
↓ More
More Items
Page 3:(Shown only when OAT Fail is selected)
--Alarm Help--
1. Verify sensor wire integrity.
2. Verify sensor resistance (See APPENDIX page 70).
↓ More
More Items
Page 4:(Shown only when OAT Fail is selected)
--Alarm Help--
3. See Paragraph 10.0 for more troubleshooting info.
4. Replace sensor.
5. Contact technical support: 800-695-1901
↓ Menu Top
Returns to the top of the menu (Page 2)
Press the Esc button to go to page 1
Page 2: (Shown only when ER Wheel Temp Fail is selected)
--Alarm Help--
ER Wheel Discharge Air Temperature sensor has failed. Sensor
reading of -60 = open circuit and a reading of 225 = shorted
circuit
↓ More
More Items
Page 3:(Shown only when ER Wheel Temp Fail is selected)
--Alarm Help--
1. Verify sensor wire integrity.
2. Verify sensor resistance (See APPENDIX page 70).
↓ More
More Items
Page 4: (Shown only when ER Wheel Temp Fail is selected)
--Alarm Help--
3. See Paragraph 10.0 for more troubleshooting info.
4. Replace sensor.
5. Contact technical support: 800-695-1901
↓ Menu Top
Returns to the top of the menu (Page 2)
Press the Esc button to go to menu page 1
Page 2: (Shown only when ER Wheel Hum Fail is selected)
--Alarm Help--
ER Wheel Discharge Air Humidity sensor has failed. System sets
default reading to 100%.
↓ More
More Items
Page 3: (Shown only when ER Wheel Hum Fail is selected)
--Alarm Help--
1. Verify sensor wire integrity.
2. Verify dc voltage (0-5vdc) from sensor.
↓ More
More Items
Page 4: (Shown only when ER Wheel Hum Fail is selected)
--Alarm Help--
3. See Paragraph 10.0 for more troubleshooting info.
4. Replace sensor.
5. Contact technical support: 800-695-1901
↓ Menu Top
Returns to the top of the menu (Page 2)
Press the Esc button to go to page 1
Page 2: (Shown only when VOC/CO2 Alarm is selected)
--Alarm Help--
VOC/CO2 Reading is above the alarm setpoint.
Press the Esc button to go to menu page 1
Page 2: (Shown only when SA Fan Fail is selected)
--Alarm Help--
The Supply Air Fan is commanded “ON” but there is no status
from the pressure switch. "ON" status is shown with a closed
contact on DI-1
↓ More
More Items
Page 3: (Shown only when SA Fan Fail is selected)
--Alarm Help--
First Reset Unit! If Fan does not start:
1. Verify “ON” command from controller.
↓ More
More Items
Page 4: (Shown only when SA Fan Fail is selected)
--Alarm Help--
2. Verify contactor is closed.
3. If OA Damper is installed, verify end switch is closed.
↓ More
More Items
Page 5: (Shown only when SA Fan Fail is selected)
--Alarm Help--
4. See Paragraph 10.0 for more troubleshooting info.
5. Contact technical support: 800-695-1901
↓ More
More Items
Page 6: (Shown only when SA Fan Fail is selected)
Control Display
Description
Page 1:
--Alarm Help--
Unit DAT Fail
Opens The Unit Discharge Air Temperature Failure Help
OAT Fail
Opens The Outside Air Temperature Failure Help
ER Wheel Temp Fail
Opens The Energy Recovery Wheel Discharge Air Temperature Failure Help
ER Wheel Hum Fail
Opens The Energy Recovery Wheel Discharge Air Humidity Failure Help
VOC/CO2 Alarm
Opens the VOC/CO2 Alarm Help
SA Fan Fail
Opens the Supply Air Fan Failure Help
EA Fan Fail
Opens the Exhaust Air Fan Failure Help
HP General Alarm
Opens the Heat Pump General Alarm Help
4way Valve Fail
Opens the Changeover Solenoid Valve Failure Help
Hi OAT Lockout
Opens the High Outside Air Temperature Lockout Help
Dirty Filter Alarm
Opens the Dirty Filter Alarm Help
Shutdown DI Alarm
Opens the Shutdown DI Alarm Help
System Restart
Opens the System Restart Help
Unit Lockout Alarm
Open the Unit Lockout Alarm Help
Low Limit Alarm
Opens the Low Limit Alarm Help
Cripple Mode Alarm
Open the Cripple Alarm Help
Wheel Maintenance
Open the Energy Recovery Wheel Maintenance Help
BAS Shutdown Alarm Opens the BAS Shutdown Alarm Help
↓ Menu Top
Returns to the top of the menu
12. ALARM HELP MENU
To access a certain menu, use the up or down arrow button. At the selected menu, press the enter button. Use the Esc button to get
back to the Main Menu.