beautypg.com

Reznor ZQYRA Unit Installation Manual User Manual

Page 29

background image

Form I-ZQYRA P/N 260414R5, Page 29

Energy Recovery Wheel

Control

Upon proof of the supply air and exhaust air fans, the controller will start the energy

recovery wheel. The unit controller will monitor the wheel discharge air temperature

and humidity and will calculate the leaving air dewpoint.

Heat Pump Control

The heat pump is controlled to maintain the discharge air temperature. When the heat

pump is in a defrost state, electric heat coils (5kW on Size 8; 10kW on Size 10) are

activated to ensure the discharge air stays at a comfortable temperature.
There are four pre-configured types of control for the heat pump. Dewpoint control

(default); Dewpoint with heating/cooling setpoint with outside air changeover (heating/

cooling setpoints only used when dewpoint is below setpoint); Dewpoint with heating/

cooling setpoint with space temperature changeover (heating/cooling setpoints only

used when dewpoint is below setpoint); and Dewpoint with outside air temperature

reset (reset setpoints only used when dewpoint is below setpoint). The heat pump

control configuration can be found from the main menu under Service Menu/

Config/Edit Equipment Config. The setpoint to adjust is called

Temp Cntrl and the

selectable options are

Dp (Dewpoint), HtgClgOa (heating/cooling setpoint with

outside air changeover),

HtgClgSpc (heating/cooling setpoint with space temperature

changeover), and

OAReset (outside air temperature reset). The following sequence

defines each control type.
Heat Pump Control Using Dewpoint Only (Default Configuration) - Upon proof of

the supply and exhaust air fans, the unit controller shall monitor the wheel leaving air

dewpoint.

If the dewpoint is above the Dewpoint Changeover Setpoint (

DpCngOvrLt =

59°F/15°C), the unit will enable the heat pump and modulate the system to

maintain a unit leaving discharge temperature high dewpoint setpoint

(DatSpHiDp

= 58°F/14°C).

If the dewpoint is below the Dewpoint Changeover Setpoint (

DpCngOvrLt =

59°F/15°C), the unit will enable the heat pump and modulate the system to

maintain a unit leaving discharge temperature low dewpoint setpoint

(DatSpLoDp

= 70°F/21°C).

Heat Pump Control Using Dewpoint with Heat/Cool Setpoints with Outside Air

Changeover - Upon proof of the supply and exhaust air fans, the unit controller shall

monitor the wheel leaving air dewpoint.

If the dewpoint is above the Dewpoint Changeover Setpoint (

DpCngOvrLt =

59°F/15°C), the unit will enable the heat pump and modulate the system to

maintain a unit leaving discharge temperature high dewpoint setpoint (

DatSpHiDp

= 58°F/14°C).

If the dewpoint is below the Dewpoint Changeover Setpoint (

DpCngOvrLt =

59°F/15°C), the unit will enable the heat pump and modulate the system to

maintain a unit leaving discharge temperature low dewpoint heating and cooling

setpoint based on the OA conditions.

o Once the OA temperature is above the outside air changeover setpoint

(

OaCngOvr = 65°F/18.3°C), the unit will maintain the leaving discharge

temperature cooling setpoint low dewpoint (

DatClgSpLoDp = 60°F/15.5°C).

space when the unit is in the occupied condition. This configuration also allows the unit

to monitor the CO

2

or VOC level and override the unit “on” when the level is above the

setpoint. Setting the sensor control setpoint to monitor will allow you to just monitor the

VOC or CO

2

levels but the unit will not react to the levels.

Required Setpoint Settings: Sch Cmd - On/Off

Occupancy -

Type 8

CN Option -

CN5

Schedule -

[Local] or BAS

DI Override -

[Off] or On

Sensor -

[CO

2

] or VOC

CO

2

or VOC Level -

Current Reading

CO

2

or VOC Setpoints -

[800] / 60

CO

2

or VOC Off Diff -

[50] / 15

Minimum Run Time -

[5 minutes]

Alarm - [

Enable] or Disable