8.0 Controls
(cont’d)
8.7 Optional Communication Cards (cont’d)
8.7.1 BACnet
®
MSTP (Option BHB8) Communication (cont’d)
Name
Description
Read/
Write
BACnet
®
MSTP
Limits
Default
Setpoints
Address Units
ErDaDp
Energy Recovery DA dewpoint
R
AV19
-
-
UnitDat
Unit DAT (AI_2)
R
AV20
-
-
Integer Values
Note: 0 = Off, 1 = Starting, 2 = Running, 3 = Test, 4 = Cripple, 5 = SysRestart, 6 = SysShutdwn
UnitMode
Unit Operation Mode
R
AV1001
-
-
Note: 1=Local Sch OFF, 2=St/St DI OFF, 3=BAS OFF, 4=VOC/CO2 OFF, 5=TEST OFF, 6=SAFETY DI OFF, 7=ALARM OFF, 8=Local Sch ON,
9=St/St DI ON, 10=BAS ON, 11=VOC/CO2 ON, 12=TEST ON
UnitCmd
Unit On/Off Command Status
R
AV1002
-
-
CompPerc
Modulation Compressor Output Percentage
R
AV1003
-
-
VocCo2
VOC or CO2 Sensor Output
R
AV1004
-
-
FanRunTm
Fan Runtime
R
AV1005
-
-
CompRunTm
Compressor Runtime
R
AV1006
-
-
ErwRunTm
Energy Recovery Wheel Runtime
R
AV1007
-
-
PreHtRunTm
Preheat Runtime Time
R
AV1008
-
-
FiltrRunTm
Filter Runtime
R
AV1009
-
-
Note: 0=Dewpoint (Default), 1=Dewpoint with OA changeover of Htg/Clg Setpoint, 2=Dewpoint with OA reset of Htg/Clg Setpoint, 3=Dewpoint with
Space changeover of Htg/Clg Setpoint
TempCntrl
Temp Control Type
R
AV1010
-
-
Note: 0=off, 1=Heating, 2=Cooling
HP_Status
Heatpump Status
R
AV1011
-
-
Note: 0=Dewpoint (Default), 1=Dewpoint with OA changeover of Htg/Clg Setpoint, 1=Dewpoint with OA reset of Htg/Clg Setpoint, 1=Dewpoint with
Space changeover of Htg/Clg Setpoint
HOA_Stat
HOA Status
R
AV1012
-
-
Digital
BAS_OffOn
BAS OffOn command
R/W
BV1
On/Off
Off
SafStatus
Supply Fan Pressure Switch Status (DI_1)
R
BV2
-
-
EafStatus
Exhaust Fan Pressure Switch Status (DI_2)
R
BV3
-
-
DiOffOn
DI On/Off Switch Status (DI_3)
R
BV4
-
-
CompAlmDi
Digital Compressor General Alarm DI Status (DI_4)
R
BV5
-
-
SafetyDI
Safety Input DI Status (DI_5)
R
BV6
-
-
FanGenAlDi
Fan General Alarm DI Status (DI_6)
R
BV7
-
-
FilterDi
Filter DI Status (DI_7)
R
BV8
-
-
FanCmd
Fan Relay (DO-1)
R
BV9
-
-
ErwCmd
Energy Recovery Wheel Relay (DO-3)
R
BV10
-
-
CompCmd
Compressor Command
R
BV11
-
-
RevVlvCmd
Reversing Valve Cmd Relay (DO-2)
R
BV12
-
-
PreHtCmd
Auxiliary heat stage output Relay (DO-4)
R
BV13
-
-
AlarmLight
Alarm output Relay (DO-5)
R
BV14
-
-
SafFailAlm
Supply Air Fan Failure Alarm (Critical Alarm)
R
BV15
-
-
EafFailAlm
Exhaust Air Fan Failure Alarm (Critical Alarm)
R
BV16
-
-
SafetyAlm
Safety Input Alarm (Critical Alarm)
R
BV17
-
-
OatAlm
Outside air temperature sensor failure Alarm (Cripple)
R
BV18
-
-
UnitDatAlm
Unit discharge air temperature sensor failure Alarm (Critical Alarm)
R
BV19
-
-
ErDatAlm
Energy Recovery DAT sensor failure (Cripple)
R
BV20
-
-
ErDahAlm
ER DA Humidity failure (Cripple)
R
BV21
-
-
RevVlvAlm
Reversing Valve Failure Alarm (Cripple)
R
BV22
-
-
DirtyFiltr
Dirty Filter Alarm (General)
R
BV23
-
-
FanGenAlm
Fan General Alarm (Critical Alarm)
R
BV24
-
-
CompGenAlm
Digital Compressor General Alarm (Cripple)
R
BV25
-
-
TestMode
Unit in Test Mode (General)
R
BV26
-
-
RestartAlm
System in restart Mode. System will auto restart after 60 mins.
R
BV27
-
-
ShutdnAlm
System in Shutdown Mode. Manual Restart Required.
R
BV28
-
-
RstAllRts
Reset All Runtimes
R/W
BV29
-
-
RstPhtRts
Reset PreHt Runtimes
R/W
BV30
-
-
RstFanRts
Reset Fan Runtimes
R/W
BV31
-
-
RstCompRts
Reset Comp Runtimes
R/W
BV32
-
-
RstFltrRts
Reset Filter Runtm
R/W
BV33
-
-
RstErwRts
Reset ERW Runtimes
R/W
BV34
-
-
FanHrsAlm
Fan run hours alarm (General)
R
BV35
-
-
CompHrsAlm
Compressor run hours alarm (General)
R
BV36
-
-
ErwHrsAlm
Wheel run hours alarm (General)
R
BV37
-
-
PhtHrsAlm
Preheat run hours alarm (General)
R
BV38
-
-
FiltHrsAlm
Filter run hours alarm (General)
R
BV39
-
-
BAS_Shtdwn
BAS Unit Shutdown
R/W
BV40
BAS_AlmRst
BAS Alarm Reset
R/W
BV41
BACnet
®