beautypg.com

0 controls (cont’d), 7 optional communication cards (cont’d), 1 bacnet – Reznor ZQYRA Unit Installation Manual User Manual

Page 54: Mstp (option bhb8) communication (cont’d), Bacnet, Mstp points list (cont’d)

background image

Form I-ZQYRA P/N 260414R5, Page 54

8.0 Controls

(cont’d)

8.7 Optional Communication Cards (cont’d)

8.7.1 BACnet

®

MSTP (Option BHB8) Communication (cont’d)

Name

Description

Read/

Write

BACnet

®

MSTP

Limits

Default

Setpoints

Address Units

ErDaDp

Energy Recovery DA dewpoint

R

AV19

-

-

UnitDat

Unit DAT (AI_2)

R

AV20

-

-

Integer Values

Note: 0 = Off, 1 = Starting, 2 = Running, 3 = Test, 4 = Cripple, 5 = SysRestart, 6 = SysShutdwn

UnitMode

Unit Operation Mode

R

AV1001

-

-

Note: 1=Local Sch OFF, 2=St/St DI OFF, 3=BAS OFF, 4=VOC/CO2 OFF, 5=TEST OFF, 6=SAFETY DI OFF, 7=ALARM OFF, 8=Local Sch ON,

9=St/St DI ON, 10=BAS ON, 11=VOC/CO2 ON, 12=TEST ON

UnitCmd

Unit On/Off Command Status

R

AV1002

-

-

CompPerc

Modulation Compressor Output Percentage

R

AV1003

-

-

VocCo2

VOC or CO2 Sensor Output

R

AV1004

-

-

FanRunTm

Fan Runtime

R

AV1005

-

-

CompRunTm

Compressor Runtime

R

AV1006

-

-

ErwRunTm

Energy Recovery Wheel Runtime

R

AV1007

-

-

PreHtRunTm

Preheat Runtime Time

R

AV1008

-

-

FiltrRunTm

Filter Runtime

R

AV1009

-

-

Note: 0=Dewpoint (Default), 1=Dewpoint with OA changeover of Htg/Clg Setpoint, 2=Dewpoint with OA reset of Htg/Clg Setpoint, 3=Dewpoint with

Space changeover of Htg/Clg Setpoint

TempCntrl

Temp Control Type

R

AV1010

-

-

Note: 0=off, 1=Heating, 2=Cooling

HP_Status

Heatpump Status

R

AV1011

-

-

Note: 0=Dewpoint (Default), 1=Dewpoint with OA changeover of Htg/Clg Setpoint, 1=Dewpoint with OA reset of Htg/Clg Setpoint, 1=Dewpoint with

Space changeover of Htg/Clg Setpoint

HOA_Stat

HOA Status

R

AV1012

-

-

Digital

BAS_OffOn

BAS OffOn command

R/W

BV1

On/Off

Off

SafStatus

Supply Fan Pressure Switch Status (DI_1)

R

BV2

-

-

EafStatus

Exhaust Fan Pressure Switch Status (DI_2)

R

BV3

-

-

DiOffOn

DI On/Off Switch Status (DI_3)

R

BV4

-

-

CompAlmDi

Digital Compressor General Alarm DI Status (DI_4)

R

BV5

-

-

SafetyDI

Safety Input DI Status (DI_5)

R

BV6

-

-

FanGenAlDi

Fan General Alarm DI Status (DI_6)

R

BV7

-

-

FilterDi

Filter DI Status (DI_7)

R

BV8

-

-

FanCmd

Fan Relay (DO-1)

R

BV9

-

-

ErwCmd

Energy Recovery Wheel Relay (DO-3)

R

BV10

-

-

CompCmd

Compressor Command

R

BV11

-

-

RevVlvCmd

Reversing Valve Cmd Relay (DO-2)

R

BV12

-

-

PreHtCmd

Auxiliary heat stage output Relay (DO-4)

R

BV13

-

-

AlarmLight

Alarm output Relay (DO-5)

R

BV14

-

-

SafFailAlm

Supply Air Fan Failure Alarm (Critical Alarm)

R

BV15

-

-

EafFailAlm

Exhaust Air Fan Failure Alarm (Critical Alarm)

R

BV16

-

-

SafetyAlm

Safety Input Alarm (Critical Alarm)

R

BV17

-

-

OatAlm

Outside air temperature sensor failure Alarm (Cripple)

R

BV18

-

-

UnitDatAlm

Unit discharge air temperature sensor failure Alarm (Critical Alarm)

R

BV19

-

-

ErDatAlm

Energy Recovery DAT sensor failure (Cripple)

R

BV20

-

-

ErDahAlm

ER DA Humidity failure (Cripple)

R

BV21

-

-

RevVlvAlm

Reversing Valve Failure Alarm (Cripple)

R

BV22

-

-

DirtyFiltr

Dirty Filter Alarm (General)

R

BV23

-

-

FanGenAlm

Fan General Alarm (Critical Alarm)

R

BV24

-

-

CompGenAlm

Digital Compressor General Alarm (Cripple)

R

BV25

-

-

TestMode

Unit in Test Mode (General)

R

BV26

-

-

RestartAlm

System in restart Mode. System will auto restart after 60 mins.

R

BV27

-

-

ShutdnAlm

System in Shutdown Mode. Manual Restart Required.

R

BV28

-

-

RstAllRts

Reset All Runtimes

R/W

BV29

-

-

RstPhtRts

Reset PreHt Runtimes

R/W

BV30

-

-

RstFanRts

Reset Fan Runtimes

R/W

BV31

-

-

RstCompRts

Reset Comp Runtimes

R/W

BV32

-

-

RstFltrRts

Reset Filter Runtm

R/W

BV33

-

-

RstErwRts

Reset ERW Runtimes

R/W

BV34

-

-

FanHrsAlm

Fan run hours alarm (General)

R

BV35

-

-

CompHrsAlm

Compressor run hours alarm (General)

R

BV36

-

-

ErwHrsAlm

Wheel run hours alarm (General)

R

BV37

-

-

PhtHrsAlm

Preheat run hours alarm (General)

R

BV38

-

-

FiltHrsAlm

Filter run hours alarm (General)

R

BV39

-

-

BAS_Shtdwn

BAS Unit Shutdown

R/W

BV40

BAS_AlmRst

BAS Alarm Reset

R/W

BV41

BACnet

®