Warning, 2 supply wiring, Supply wiring connections – Reznor ZQYRA Unit Installation Manual User Manual

Page 15: Mca and mop

background image

Form I-ZQYRA P/N 260414R5, Page 15

Supply Wiring

Connections

FIGURE 15A illustrates supply wiring connections with or without Option BA6 discon-

nect switch.

DISCONNECT SWITCH

GND

OPTIONAL FUSIBLE

#6 BK

#6 Y

#6 R

208 or 230/3/60

DISCONNECT SWITCH

60A LOCKABLE ON/OFF

Option BA6

A

B

C

Distribution

Blocks in

the Electrical

Compartment

Field installed wiring (If there is no Option BA

disconnect switch, connect field wires at A, B,

and C in the electrical compartment.)

460/3/60

FIGURE 15A - Supply

Wiring Connections -

Option AK20 and AK7

7.2 Supply Wiring

Depending on option selection, the unit is wired for either 208-230/3ph/60Hz (Option

AK20) or 460/3ph/60Hz (Option AK7).
FIGURE 15B illustrates the field wiring change required when using 230V supply. If a

unit is ordered with Option AK20 (208-230/60), it is factory-wired for 208V operation.

When connecting to a 230V supply, a field wiring change is required.

a) In the electrical compartment, locate terminal blocks L5 and L6.

b) Disconnect the red wire from Terminal L5.

c) Connect the red wire to Terminal L6.

(O)

(R)

(BK)

A

C

14 Gauge Red Wire

14 Gauge Black Wire

}

TRANSFORMER

TO 75VA

TERMINAL BLOCKS

(in the electrical compartment)

L5
L6

A

DISTRIBUTION BLOCKS

(2 of 3 in the electrical compartment)

Wiring Connections for Option AK20 (208-230V):
-- For units ordered with AK20 (208-230V), the factory connects the 14 gauge red wire to Terminal L5.

-- Using 230V supply, locate Terminal L5. Disconnect the 14 gauge red wire from Terminal L5.

Connect the 14 gauge red wire to Terminal L6.

-- Using 208V supply, no change required.

= Distribution block to transformer factory wiring for units ordered with Option AK20.

= When using 230V supply, connect the 14 gauge red wire to Terminal L6.

Key:

FIGURE 15B - Wire

Connection Change

Required when using

230V Supply

Supply Voltage

Supply Fan

Motor

Exhaust Fan

Motor

Supply Wiring and Connection

(See FIGURES 15A and 15B.)

Option AK20

(208-230/3ph/60Hz)

Direct drive

ECM (3ph)

Direct drive

ECM (3ph)

Shipped as 208V; field convertible to 230V. See instructions

above (FIGURE 15B) and on the wiring diagram.

Option AK7 (460/3ph/60Hz) Direct drive

ECM (3ph)

Direct drive

ECM (3ph)

Standard 3ph/60Hz

Model ZQYRA

ECM

Supply

Fan

ECM

Exhaust

Fan

Compressor

Energy

Wheel

Control

Transformer

Supplemental

Electric Heat

(Standard)

Standard Model Z

(without Optional

Electric PreHeat)

Optional Electric

PreHeat

Model ZQYRA

unit with Optional

Electric PreHeat

Voltage

Size

FLA

FLA

MCC LRA RLA

FLA

VA

FLA

kW

FLA

FLA MCA MOP

Opt

kW

FLA

FLA

MCA MOP

208-230/3/60

(Option AK20)

8

3.0

5.2

18.2 88.0 11.7

0.7

150.0 0.7

5

11.

21.3 24.2 35

PH1A

5.0

11.5

32.8 38.6 45

PH2A 10.0 23.1

44.3 53.0 70

12

3.0

9.7

25.1 110.0 16.1

0.6

150.0 0.7

10

23.1

37.1 45.3 60

PH1A

5.0

11.5

48.6 56.8 70

PH2A 10.0 23.1

60.1 68.3 80

460/3/60

(Option AK7)

8

1.7

2.6

9.6 44.0 6.2

0.35 150.0 0.3

5

5.8

11.1 12.7 15

PH1A

5.0

5.8

16.9 19.9 20

PH2A 10.0 11.5

22.7 27.1 35

12

1.7

4.6

12.1 52.0 7.8

0.35 150.0 0.3

10

11.5

18.5 22.5 30

PH1A

5.0

5.8

24.3 37.2 40

PH2A 10.0 11.5

30.0 34.1 40

NOTE: For 208-230/3/60 V, Control Transformer FLA is calculated using the worst case (208V).
NOTE: For 208-230/3/60 V, Electric Heat FLA is calculated using the worst case.

MCA and MOP

WARNING

To prevent injury or death due to electrocution or contact with moving parts, lock

disconnect switch open. See Hazard Levels, page 2.