beautypg.com

0 controls (cont’d) – Reznor ZQYRA Unit Installation Manual User Manual

Page 30

background image

Form I-ZQYRA P/N 260414R5, Page 30

o Once the OA temperature falls below the outside air changeover setpoint

(

OaCngOvr = 65°F/18.3°C) by the difference of the outside air changeover

deadband (

OaCngOvrDb = 2°), the unit will maintain the leaving discharge

temperature heating setpoint low dewpoint (

DatHtgSpLoDp = 70°F/21°C).

Heat Pump Control Using Dewpoint with Heat/Cool Setpoints with Space Change-

over - Upon proof of the supply and exhaust air fans, the unit controller shall monitor

the wheel leaving air dewpoint.

If the dewpoint is above the Dewpoint Changeover Setpoint (

DpCngOvrLt =

59°F/15°C), the unit will enable the heat pump and modulate the system to

maintain a unit leaving discharge temperature high dewpoint setpoint (

DatSpHiDp

= 58°F/14°C).

If the dewpoint is below the Dewpoint Changeover Setpoint (

DpCngOvrLt =

59°F/15°C), the unit will enable the heat pump and modulate the system to

maintain a unit leaving discharge temperature low dewpoint heating and cooling

setpoint based on the space conditions.

o Once the zone temperature is above the zone changeover setpoint (

ZnCngOvr

= 70°F/21°C), the unit will maintain the leaving discharge temperature cooling

setpoint low dewpoint (

DatClgSpLoDp = 60°F/15.5°C).

o Once the zone temperature falls below the zone air changeover setpoint

(

ZnCngOvr = 70°F/21°C) by the difference of the zone changeover deadband

(

ZnCngOvrDb = 2°), the unit will maintain the leaving discharge temperature

heating setpoint low dewpoint (

DatHtgSpLoDp = 70°F/21°C).

Heat Pump Control Using Dewpoint with Outside Air Reset - Upon proof of the

supply and exhaust air fans, the unit controller shall monitor the wheel leaving air

dewpoint.

If the dewpoint is above the Dewpoint Changeover Setpoint (

DpCngOvrLt =

59°F/15°C), the unit will enable the heat pump and modulate the system to

maintain a unit leaving discharge temperature high dewpoint setpoint (

DatSpHiDp

= 58°F/14°C).

If the dewpoint is below the Dewpoint Changeover Setpoint (

DpCngOvrLt =

59°F/15°C), the unit will enable the heat pump and modulate the system to

maintain a unit leaving discharge temperature low dewpoint heating and cooling

setpoint based on the OA reset conditions.

o If the OA temperature is at or below the outside air low setpoint low dewpoint

(

OaLoSpLoDp = 50°F/10°C), the unit will maintain the discharge air high

setpoint low dewpoint (

DaHiSpLoDp = 70°F/21°C).

o If the OA temperature is at or above the outside air high setpoint low dewpoint

(

OaHiSpLoDp = 70°F/21°C), the unit will maintain the discharge air low

setpoint low dewpoint (

DaLoSpLoDp = 60°F/15.5°C).

o The discharge air setpoint is reset linearly from the discharge air high setpoint

low dewpoint to the discharge air low setpoint low dewpoint as the outside air

changes.

Reversing Valve Operation:

Whenever the system calls for heating mode, the sys-

tem will energize (close relay and power valve) the reversing valve. This will reverse

the refrigerant flow and allow the system to provide heating. Whenever the system

calls for cooling mode the reversing valve is de-energized (no power at valve).

Optional PreHeat Control, Option PH1A (5kW) and PH2A (10kW)

The unit controller will monitor the outside air temperature, and if the temperature is

below the Preheat Enable Setpoint (

PreHtEnSP = 0°F/-17.7°C), the system will enable

the optional electric preheat coil(s). The optional preheat coil(s) will remain enabled

until the outside air temperature is above the outside air enable temperature by the

Preheat Enable Deadband (

PreHtEnDb = 5°F/3°C).

If Option PH1A or PH2A is not installed, the controller will hide all data associated with

the preheat coil.

8.3 Safeties, Alarms,

and Lockouts

8.2 Sequence of

Operation

(cont’d)

8.0 Controls

(cont’d)

Heat Pump Controls

(cont’d)

The system has two types of alarms built-in. The first type is all of the service alarms.

Service alarms are alarms that cause the system to react in a particular sequence as

described in Paragraph 8.3.1. Service alarms include alarms like fan failure, low limit

alarm, and heat pump failure.