beautypg.com

0 electrical connections and wiring (cont’d), 3 electrical compartment, 4 electrical components – Reznor ZQYRA Unit Installation Manual User Manual

Page 16: 1 fan motors, Figure 16 - control locations, Locations of components, Control compartment with access panel removed

background image

Form I-ZQYRA P/N 260414R5, Page 16

FIGURE 16 -

Control

Locations

7.3 Electrical

Compartment

Locations of Components

Remove the electrical compartment access panel to view the controls and compressor

as illustrated in

FIGURE 16. Some components in the electrical compartment are com-

mon and some vary by options selected.

7.0 Electrical Connections and Wiring (cont’d)

7.4.1 Fan Motors

The supply and exhaust fans are centrifugal, backward curve fans with integral elec-

tronically commutated motors (ECM) that are directly controlled by the unit interface

control. The unit uses a portion of the outside intake air as part of the return airflow as

shown in

FIGURE 17.

At startup, the speed of each fan must be set. See the instructions in Paragraph 9.3

7.4 Electrical

Components

FIGURE 17 - Diagram showing Airflow through the Unit

Ou

tsi

de

Air Inlet

Exhaust

Air

Supply

Air

Return

Air

WHEEL

NOTE: If installing this ventilation unit

indoors, exhaust and supply airflow will be

double. Ductwork and louvers must be sized

accordingly.
(Size 8 - CFM Range is 500-1100;

Size 12 - CFM Range is 900-1500)
Example: A Model ZQYRA installed indoors

operating at 1500 cfm will require supply and

exhaust ductwork sized for 3000 cfm.

Option BE18

Dirty Filter

Switch

Air Proving Switch

(exhaust side),

P/N 197031 set

at 0.35” w.c.

Air Proving Switch

(supply side),

P/N 197031 set

at 0.35” w.c.

Supply &

Exhaust Fan

Overload Relays

Contactor (optional

electric preheat)

Contactor

(wheel)

Contactor (fans)

Multi Voltage

Relay Module

(time

schedule

clock,

Opt CN7A)

Distribution

Blocks -

A, B, and C

Contactor

(heat pump)

Grounding

Lug

Digital Controller

(Compressor)

Control Transformer

(damper motor)

Control

Transformers

Unit Controller

(NOTE: If ordered

with a BACnet®

or LONworks®

communication

card, it is located

on the controller;

see Paragraph 8.7.)

Field

Connection

Terminal

Blocks

Display

Module

Terminal Blocks

Transformer

(Size 8, 460V)

Contactor

(supplemental

heating element)

Relay

(damper motor)

Controls on either the side or

back wall of the Control

Compartment

Electrical

Panel

Control Compartment

with Access Panel

Removed