Chapter 5 Serial Communication

100

5

Setting communication parameters 2 (When the PLC link is not used)

Handshaking
protocol 1

Function

Command

Response Description

Change

WP07n

OK

n = 0: No handshaking
n = 1: Use protocol

Confirm

RP07

07n

Handshaking
protocol 2

Change

OK

n = 0: PASS/RTRY
protocol

n = 1: ACK/NAK protocol

RP08

Confirm

08n

Header

Change

WP08n

WP51hhh... OK

hhh... = Header (up to
five characters)
* To set a header, use
HEX (hexadecimal)
codes.
* hhh... = FF: Header is
not set.

Confirm

RP51

51hhh...

Delimiter

Change

WP52hhh... OK

hhh... = Delimiter (up to
five characters)
* To set a delimiter, use
HEX (hexadecimal)
codes.
* hhh... = FF: Delimiter is
not set.

Confirm

RP52

52hhh...

*To set details of the
protocol, use handshak-
ing protocol 2.

Error code

00, 02,

05, 07,

14

00, 02,

05, 06,

10, 12,

14

To set the header and delimiter, send the following command:

Example

Set the communication data format to 01 bar code data A .

Tips

WP51013031

SOH 0

1

SOH

*

=01h, 0=30h, 1=31h, A=41h, CR =0Dh

WP52410D

A CR

Adding
checksum

Change

WP39n

OK

n = 0: Do not add

n = 1: Add

Confirm

RP39

39n