Wiring guidelines – Rockwell Automation 2097-Vxxx Kinetix 350 Single-axis EtherNet/IP Servo Drive User Manual User Manual
Page 62
62
Rockwell Automation Publication 2097-UM002C-EN-P - December 2013
Chapter 4 Connect the Kinetix 350 Drive System
Wiring Guidelines
Use these guidelines as a reference when wiring the connectors on your
Kinetix 350 drive power modules.
Follow these steps when wiring the connectors on your Kinetix 350 drive
modules.
1. Prepare the wires for attachment to each connector plug by removing
insulation equal to the recommended strip length.
2. Route the cable/wires to your Kinetix 350 drive.
3. Insert wires into connector plugs.
Refer to connector pinout tables in
diagrams in
4. Tighten the connector screws.
5. Gently pull on each wire to make sure it does not come out of its terminal;
reinsert and tighten any loose wires.
6. Insert the connector plug into the module connector.
IMPORTANT
For connector locations of the Kinetix 350 drives, refer to
When tightening screws to secure the wires, refer to the tables beginning on
for torque values.
When removing insulation from wires, refer to the tables beginning on
IMPORTANT
To improve system performance, run wires and cables in the wireways as
established in
.
IMPORTANT
Use caution not to nick, cut, or otherwise damage strands as you
remove the insulation.