Connect the Kinetix 350 Drive System
Basic Wiring Requirements
This section contains basic wiring information for the Kinetix 350 drive.
Topic
Page
Grounding Your Kinetix 350 Drive System
Wiring the Kinetix 350 Drive Connectors
Apply the Motor Cable Shield Clamp
Feedback and I/O Cable Connections
Wiring the Feedback and I/O Connectors
Kinetix 350 Drive (IOD connector and terminal block)
ATTENTION: Plan the installation of your system so that you can perform all
cutting, drilling, tapping, and welding with the system removed from the
enclosure. Because the system is of the open type construction, be careful to
keep any metal debris from falling into it. Metal debris or other foreign matter
can become lodged in the circuitry, which can result in damage to components.
SHOCK HAZARD: To avoid hazard of electrical shock, perform all mounting and
wiring of the Bulletin 2097 drive prior to applying power. Once power is applied,
connector terminals can have voltage present even when not in use.
IMPORTANT
This section contains common PWM servo system wiring configurations, size,
and practices that can be used in a majority of applications. National Electrical
Code, local electrical codes, special operating temperatures, duty cycles, or
system configurations take precedence over the values and methods provided.