Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual
Page 61
Rockwell Automation Publication 20B-UM002G-EN-P - July 2014
61
Programming and Parameters
Chapter 1
INPUT
S & OUTPUTS
An
al
og O
u
tpu
ts
342
345
[Analog Out1 Sel]
[Analog Out2 Sel]
Selects the source of the value that drives the
analog output.
Default:
Options:
0 “Output Freq”
See Table
001
002
003
004
005
007
006
012
135
136
137
138
220
219
343
346
[Analog Out1 Hi]
[Analog Out2 Hi]
Sets the analog output value when the source
value is at maximum.
Default:
Min/Max:
Units:
20.000 mA, 10.000 Volts
0.000/20.000mA
–/+10.000V
0.001 mA
0.001 Volt
344
347
[Analog Out1 Lo]
[Analog Out2 Lo]
Sets the analog output value when the source
value is at minimum.
Default:
Min/Max:
Units:
0.000 mA, 0.000 Volts
0.000/20.000mA
–/+10.000V
0.001 mA
0.001 Volt
354
355
[Anlg Out1 Scale]
[Anlg Out2 Scale]
Sets the high value for the range of analog out
scale. Entering 0.0 will disable this scale and max
scale will be used. Example: If [Analog Out Sel] =
“Commanded Trq,” a value of 150 = 150% scale
in place of the default 800%.
Default:
Min/Max:
Units:
0.0
[Analog Out1 Sel]
0.1
Units shown are dependent on
the value in parameter 342/345.
377
378
[Anlg1 Out Setpt]
[Anlg2 Out Setpt]
Controls the analog output value from a
communication device. Example: Set [Data In Ax]
to “377” (value from communication device).
Then set [Analog Outx Sel] to “Param Cntl.”
Default:
Min/Max:
Units:
4.000 mA, 0.000 Volts
0.000/20.000 mA
–/+10.000V
0.001 mA
0.001 Volt
Fil
e
Gr
oup
No
.
Parameter Name & Description
See
page 16
for symbol descriptions
Values
Rela
ted
(1)
Refer to Option Definitions on
.
Options
[Analog Out1 Lo] Value
[Analog Out1 Hi] Value
Param. 341 = Signed
Param. 341 = Absolute
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20-23
24
25
“Output Freq”
“Command Spd”
“Output Amps”
“Torque Amps”
“Flux Amps”
“Output Power”
“Output Volts”
“DC Bus Volts”
“PI Reference”
(1)
“PI Feedback”
“PI Error”
“PI Output”
“%Motor OL”
“%Drive OL”
“CommandedTrq”
“MtrTrqCurRef”
(1)
“Speed Ref”
“Speed Fdbk”
“Pulse In Ref”
(1)
“Torque Est”
(1)
“Scale Block1-4”
(1)
“Param Cntl”
(1)
“SpdFb NoFilt
–[Maximum Speed]
–[Maximum Speed]
0 Amps
–200% Rated
0 Amps
0 kW
0 Volts
0 Volts
–100%
–100%
–100%
–100%
0%
0%
–800% Rated
–200% Rated
–[Maximum Speed]
–[Maximum Speed]
–25200.0 RPM
–800%
0 Hz
0 Hz/RPM
0 Amps
0 Amps
0 Amps
0 kW
0 Volts
0 Volts
0%
0%
0%
0%
0%
0%
0%
0%
0 Hz/RPM
0 Hz/RPM
0 Hz/RPM
0%
+[Maximum Speed]
+[Maximum Speed]
200% Rated
200% Rated
200% Rated
200% Rated
120% Rated Input Volts
200% Rated Input Volts
100%
100%
100%
100%
100%
100%
800% Rated
200% Rated
+[Maximum Speed]
+[Maximum Speed]
+[Maximum Speed]
+800%