Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual
Page 26

26
Rockwell Automation Publication 20B-UM002G-EN-P - July 2014
Chapter 1
Programming and Parameters
M
O
TO
R C
O
N
TROL
To
rq
A
ttrib
ut
es
064 [Ixo Voltage Drop]
Value of voltage drop across the leakage
inductance of the motor at rated motor current.
Used only when parameter 53 is set to “Sensrls
Vect,” “SV Economize or “FVC Vector.”
Default:
Min/Max:
Units:
Based on Drive Rating
0.0/230.0, 480.0, 575 VAC
0.1 VAC
066 [Autotune Torque]
Specifies motor torque applied to the motor
during the flux current and inertia tests
performed during an autotune.
Default:
Min/Max:
Units:
50.0%
0.0/150.0%
0.1%
067 [Inertia Autotune]
Provides an automatic method of setting [Total
Inertia]. This test is automatically run during
Start-Up motor tests. Important: If using rotate
tune for “Sensrls Vect” mode, the motor should
be uncoupled from the load or results may not be
valid. With “FVC Vector,” either a coupled or
uncoupled load will produce valid result.
“Ready” = Parameter returns to this setting
following a completed inertia tune.
“Inertia Tune” = A temporary command that
initiates an inertia test of the motor/load
combination. The motor will ramp up and down,
while the drive measures the amount of inertia.
Default:
Options:
0
0
1
“Ready”
“Ready”
“Inertia Tune”
427
431
[Torque Ref A Sel]
[Torque Ref B Sel]
Selects the source of the external torque
reference to the drive. How this reference is used
is dependent upon [Speed/Torque Mod].
(1)
See Appendix B for DPI port locations.
Default:
Options:
0
24
0
1
2
3-17
18-22
23
24
25-28
29
“Torque Stpt1”
“Disabled”
“Torque Stpt1”
“Analog In 1”
“Analog In 2”
“Reserved”
“DPI Port 1-5”
(1)
“Reserved”
“Disabled”
“Scale Block1-4”
“Torque Stpt2”
428
432
[Torque Ref A Hi]
[Torque Ref B Hi]
Scales the upper value of the [Torque Ref x Sel]
selection when the source is an analog input.
Default:
Min/Max:
Units:
100.0%
100.0%
–/+800.0%
0.1%
429
433
[Torque Ref A Lo]
[Torque Ref B Lo]
Scales the lower value of the [Torque Ref x Sel]
selection when the source is an analog input.
Default:
Min/Max:
Units:
0.0%
0.0%
–/+800.0%
0.1%
430 [Torq Ref A Div]
Defines the value of the divisor for the [Torque
Ref A Sel] selection.
Default:
Min/Max:
Units:
1.0
0.1/3276.7
0.1
434 [Torque Ref B Mult]
Defines the value of the multiplier for the [Torque
Ref B Sel] selection.
Default:
Min/Max:
Units:
1.0
–/+32767.0
0.1
435 [Torque Setpoint1]
Provides an internal fixed value for Torque
Setpoint when [Torque Ref x Sel] is set to “Torque
Setpt.”
Default:
Min/Max:
Units:
0.0%
–/+800.0%
0.1%
436 [Pos Torque Limit]
Defines the torque limit for the positive torque
reference value. The reference will not be
allowed to exceed this value.
Default:
Min/Max:
Units:
200.0%
0.0/800.0%
0.1%
Fil
e
Gr
oup
No
.
Parameter Name & Description
See
page 16
for symbol descriptions
Values
Rela
ted
FV
FV
FV
FV
FV
FV
FV
FV
FV