Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 60

background image

60

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

Chapter 1

Programming and Parameters

IN

PUTS & OUTPU

TS

An

alog In

put

s

322
325

[Analog In 1 Hi]
[Analog In 2 Hi]

Sets the highest input value to the analog input x
scaling block.
[Anlg In Config], parameter 320 defines if this
input will be –/+10V or 0-20 mA.

Default:

Min/Max:

Units:

10.000 Volt
10.000 Volt

0.000/20.000mA
–/+10.000V
0.000/10.000V
0.001 mA
0.001 Volt

091
092

323
326

[Analog In 1 Lo]
[Analog In 2 Lo]

Sets the lowest input value to the analog input x
scaling block.
[Anlg In Config], parameter 320 defines if this
input will be –/+10V or 0-20 mA.
If set below 4 mA, [Analog In x Loss] should be
“Disabled.”

Default:

Min/Max:

Units:

0.000 Volt
0.000 Volt

0.000/20.000mA
–/+10.000V
0.000/10.000V
0.001 mA
0.001 Volt

091
092

324
327

[Analog In 1 Loss]
[Analog In 2 Loss]

Selects drive action when an analog signal loss is
detected. Signal loss is defined as an analog
signal less than 1V or 2 mA. The signal loss event
ends and normal operation resumes when the
input signal level is greater than or equal to 1.5V
or 3 mA.
Note: parameter 190, [Direction Mode] must be
set to “0, Unipolar.”

Default:

Options:

0
0

0
1
2
3
4
5
6

“Disabled”
“Disabled”

“Disabled”
“Fault”
“Hold Input”
“Set Input Lo”
“Set Input Hi”
“Goto Preset1”
“Hold OutFreq”

091
092

An

al

og O

utput

s

340 [Anlg Out Config]

Selects the mode for the analog outputs. .

341 [Anlg Out Absolut]

Selects whether the signed value or absolute value of a parameter is used before being scaled to
drive the analog output.

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted

1

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 = Current

0 = Voltage
x = Reserved

Bit #

Factory Default Bit Values

Analog O

ut1

Analog O

ut2

1

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 = Absolute

0 = Signed
x = Reserved

Bit #

Factory Default Bit Values

Analog O

ut1

Analog O

ut2