Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual
Page 41

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014
41
Programming and Parameters
Chapter 1
DYNAMIC
C
ONTRO
L
Rest
ar
t M
odes
167 [Powerup Delay]
Defines the programmed delay time, in seconds,
before a start command is accepted after a power
up.
Default:
Min/Max:
Units:
0.0 Secs
0.0/10800.0 Secs
0.1 Secs
168 [Start At PowerUp]
Enables/disables a feature to issue a Start or Run
command and automatically resume running at
commanded speed after drive input power is
restored. Requires a digital input configured for
Run or Start and a valid start contact.
Default:
Options:
0
0
1
“Disabled”
“Disabled”
“Enabled”
169 [Flying Start En]
Enables/disables the function which reconnects
to a spinning motor at actual RPM when a start
command is issued.
Not required in FVC Vector mode when using an
encoder.
Default:
Options:
0
0
1
“Disabled”
“Disabled”
“Enabled”
170 [Flying StartGain]
Sets the response of the flying start function.
Important: Lower gain can be required for
permanent magnet motors.
Default:
Min/Max:
Units:
4000
20/32767
1
174 [Auto Rstrt Tries]
Sets the maximum number of times the drive
attempts to reset a fault and restart.
Default:
Min/Max:
Units:
0
0/9
1
175 [Auto Rstrt Delay]
Sets the time between restart attempts when
[Auto Rstrt Tries] is set to a value other than zero.
Default:
Min/Max:
Units:
1.0 Secs
0.5/10800.0 Secs
0.1 Secs
Fil
e
Gr
oup
No
.
Parameter Name & Description
See
page 16
for symbol descriptions
Values
Rela
ted
ATTENTION: Equipment damage and/or personal injury can result if
this parameter is used in an inappropriate application. Do not use this
function without considering applicable local, national and
international codes, standards, regulations or industry guidelines.
ATTENTION: Equipment damage and/or personal injury can result if
this parameter is used in an inappropriate application. Do Not use this
function without considering applicable local, national and
international codes, standards, regulations or industry guidelines.