Fa
u
lt
s
238 [Fault Config 1]
Enables/disables annunciation of the listed faults.
240 [Fault Clear]
Resets a fault and clears the fault queue.
Default:
Options:
0
0
1
2
“Ready”
“Ready”
“Clear Faults”
“Clr Flt Que”
241 [Fault Clear Mode]
Enables/disables a fault reset (clear faults)
attempt from any source. This does not apply to
fault codes which are cleared indirectly via other
actions.
Default:
Options:
1
0
1
“Enabled”
“Disabled”
“Enabled”
242 [Power Up Marker]
Elapsed hours since initial drive power up. This
value will rollover to 0 after the drive has been
powered on for more than the max value shown.
For relevance to most recent power up see [Fault
x Time].
Default:
Min/Max:
Units:
Read Only
0.0000/214748.3647 Hr
0.1 Hr
244
246
248
250
252
254
256
258
243
245
247
249
251
253
255
257
[Fault 1 Code]
[Fault 2 Code]
[Fault 3 Code]
[Fault 4 Code]
[Fault 5 Code]
[Fault 6 Code]
[Fault 7 Code]
[Fault 8 Code]
A code that represents the fault that tripped the
drive. The codes will appear in these parameters
in the order they occur ([Fault 1 Code] = the most
recent fault).
Default:
Min/Max:
Units:
Read Only
0/65535
0
Fil
e
Gr
oup
No
.
Parameter Name & Description
See
page 16
for symbol descriptions
Values
Rela
ted
1
1
1
0
0
0
1
0
0
0
x
0
0
0
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 = Enabled
0 = Disabled
x = Reserved
Bit #
Factory Default Bit Values
Po
w
er L
oss
UnderV
oltage
HS L
ow
Temp
(3)
Mot
or O
verL
d
Shear P
in
AutRst T
ries
Dec
el Inhibt
Mot
or T
herm
In PhaseL
oss
(1)
Load L
oss
ShearPNo A
cc
(2)
Out PhaseL
oss
(4)
PT
C HW
(1)
Default is “1” for Frames 8-10.
(2)
When enabled, the drive ignores the
shear pin fault during any accel/decel.
(3)
Firmware 6.002 and later.
(4)
If Torque Prove is enabled, Output
Phase Loss will always be performed.
(5)
Firmware 9.001 and later.
When these faults are disabled,
always change parameter 173
[DPI Loss Action] to a value of
“1” or “2.”
1
1
x
1
x
x
x
x
x
x
x
x
x
x
x
x
26
16
17
18
19
20
21
22
23
24
25
27
28
29
30
31
1 = Enabled
0 = Disabled
x = Reserved
Bit #
DPI P1 L
oss
(5)
DPI P2 L
oss
(5)
DPI P3 L
oss
(5)