Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual
Page 33

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014
33
Programming and Parameters
Chapter 1
SPEED C
OMMAND
D
iscret
e Spee
ds 108 [Jog Speed 2]
Sets the output frequency when Jog Speed 2 is
selected.
Default:
Min/Max:
Units:
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
Speed T
rim
116 [Trim % Setpoint]
Adds or subtracts a percentage of the speed
reference or maximum speed. Dependent on the
setting of [Trim Out Select], parameter 118.
Default:
Min/Max:
Units:
0.0%
–/+200.0%
0.1%
117 [Trim In Select]
Specifies which analog input signal is being used
as a trim input.
(1)
See
(2)
If selected, HIM manual control is not allowed.
Default:
Options:
2
0
1
2
3-6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23-24
25-28
“Analog In 2”
“PI Setpoint”
“Analog In 1”
“Analog In 2”
“Reserved”
“Pulse In”
“Encoder”
“MOP Level”
“Reserved”
“Preset Spd1”
“Preset Spd2”
“Preset Spd3”
“Preset Spd4”
“Preset Spd5”
“Preset Spd6”
“Preset Spd7”
“DPI Port 1”
(1) (2)
“DPI Port 2”
(1)
“DPI Port 3”
(1)
“DPI Port 4”
(1)
“DPI Port 5”
(1)
“Reserved”
“Scale Block1-4”
118 [Trim Out Select]
Specifies which speed references are to be trimmed.
119 [Trim Hi]
Scales the upper value of the [Trim In Select]
selection when the source is an analog input.
Default:
Min/Max:
Units:
60.0 Hz
–/+[Maximum Speed]
0.1 Hz
1 RPM/%
120 [Trim Lo]
Scales the lower value of the [Trim In Select]
selection when the source is an analog input.
Default:
Min/Max:
Units:
0.0 Hz
–/+[Maximum Speed]
0.1 Hz
1 RPM/%
Fil
e
Gr
oup
No
.
Parameter Name & Description
See
page 16
for symbol descriptions
Values
Rela
ted
0
0
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
Bit #
Factory Default Bit Values
Trim Ref A
Trim Ref B
Add or %
Bit 1, 0
Trimmed
Not Trimmed
1 =
0 =
Bit 2
%
Add
x = Reserved